Instruction/ maintenance manual of the product BC7000L1000 Honeywell
Go to page of 33
CONVERSION WIRING DIAGRAMS FOR BC7000L1000 The diagrams and instructions contained in this booklet are for converting the following model programmers to BC7000 Microcomputer Based Burner Control System. TABLE OF CONTENTS Page Section l . . . . . . . .
SECTION I FIREYE C, D, E-SERIES CONTROL 120 V ONLY DIRECTIONS: 1. Disconnect all power to programmer. 2. Remove old programmer from subbase (trade-in to Honeywell Authorized Flame Safeguard Distributor). 3. Mark all wires on subbase; i.e., wires connected to terminal “D” should be marked “D.
E1214A FIREYE 70D10/26CF6-5022/26 CU6-5065 EP160/EP161/EP170 TO BC7000L/PM720L2004 or 1030.
E1215B FIREYE 24CJ5 - 5010/5011/3010/3011 25CU6 5062/5063/RS-2E 70D30/26CF6 5020/5021/1010/1011 EP380/EP381/EP390 TO BC7000L/PM720M2002.
E1216E FIREYE 24CJ5 5015 70D20/26CF6 5023/25 CU65055 EP260/EP261/EP270 TO BC7000L/PM720G2005.
SECTION II FIREYE P-SERIES CONTROLS 120 V ONLY DIRECTIONS: 1. 2. 3. 4. 5. 6. 7. 8. Disconnect all power to programmer. Remove old programmer from subbase (trade-in to Honeywell Authorized Flame Safeguard Distributor). Mark all wires on subbase; i.e., wires connected to terminal “D” should be marked “D.
E1221A FIREYE 26RJ8 1016, 1016T 26RJ8 1012, 1012T, 6012, 6012T TO BC7000L + PM720G2005.
E1693 FIREYE 25RLJ84580 TO BC700L + PM720L1030.
E1217B FIREYE 25RU8 6560, 6570,6580 26RJ8 6060, 6070,6080, 6160 TO BC7000L + PM720L1030.
E1218A FIREYE 29RF5 1001, 1009, 6009 TO BC7000L + PM720G2013.
E1219A 26RJ8 6058, 6066, 6068 25RU8 6558, 6566 TO BC7000L + PM720G2005.
E1220A FIREYE 26RJ8 1002, 1003, 1008, 1011, 1018, 6008, 6018 29RF5 1000, 1002, 1005, 1015, 1104 29RF5 6015 TO BC7000L + PM720G2005.
SECTION Ill HONEYWELL R4126, R4127, R4181 CONTROLS 120 V ONLY DIRECTIONS: 1. 2. 3. 4. 5. 6. 7. 8. Disconnect all power to programmer. Remove old programmer from subbase (trade-in to Honeywell Authorized Flame Safeguard Distributor). Mark all wires on subbase; i.
E1222A R4126A1172, 1180,1198 TO BC7000L + PM720L2004.
E1223A R4126A1008, 1016, 1024, 1032, 1040, 1057, 1081, 1149 R4126B1006, 1014, 1022 TO BC7000L + PM720G2005.
E1224A R4126A1073,1164 TO BC7000L + PM720L2004.
E1753 R4127A1155 AND R4127A1197 TO BC7000L + PM720G2005.
E1225A R4127 (ALL MODELS) EXCEPT R4127A1171, R4127A1155, R4127A1197, R4127B1039, AND R4127B1047 TO BC7000L + PM720G.
E1724A R4127A1171/R4127B1039/R4127B1047 TO BC7000L+PM720G2005.
E1226A R4181A1000, R4181A1026 TO BC7000L + PM720G2005.
E1227A R4181A1018, R4181A1034 TO BC7000L + PM720L2004.
E1228A R4181A1042, R4181A1059 TO BC7000L + PM720L2004.
SECTION IV HONEYWELL R4140 AND R4150, 20 TERMINAL SUBBASE 120 V ONLY NOTE: This cross reference does not include conversions for proprietary controls such as Cleaver Brooks, Vapor or Peabody Gordon Piatt models.
REPLACING AN R4140M OR R4150M WITH START INTERLOCKS WITH A BC7000L/PM720M2002 *-X x x ;.-” .“. STEPS FOR CONVERSION 1. START INTERLOCKS BECOME PREIGNITION INTERLOCKS. 2. DISCONNECT DAMPER CONTROL WIRE FROM TERMINAL 10 CONNECT IT TO TERMINAL 11. 3.
E1237 REPLACING AN R4140M OR R4150M WITH PREIGNITION INTERLOCKS WITH A BC7000L/PM720M2002 2. DISCONNECT DAMPER CONTROL WIRE FROM TERMINAL 10 AND CONNECT IT TO TERMINAL 11. 3. 4. 5. REMOVE JUMPER FROM TERMINAL BETWEEN TERMINAL 11 AND 12 (on some models).
REPLACING AN R4140G OR R4150G WITH START INTERLOCKS WITH A BC7000L/PM720G2005 /PM720G2013 t * BC7000L/PM720G2005 /PM720G2013 STEPS FOR CONVERSION 1. START INTERLOCKS BECOME PREIGNITION INTERLOCKS. 2. 3. 4. FOR PM720G2005 ONLY JUMPER 15 TO 8 FOR 30-SECOND TRIAL FOR MAIN FLAME AT TERMINAL NO.
REPLACING AN R4140G OR R4150G WITH PREIGNITION INTERLOCKS WITH A BC7000L/PM720G2005 /PM720G2013 #f-----+--- -., ,,, ,):.> ?>., E.,li:,. ~ FOR PM720G20050NLYJ”MPER8T0 15 FOR3CISECCZNDTRIAL FOR ( +- ————=—=— —$==$ — Ji >: c, .
REPLACING AN R4140L OR R4150L WITH A BC7000L/PM720L1030 /PM720L2004 L /-.., ‘-4 ~VJIRllUG CHANGE NOT NECESSARY FOR PM720LI030 BC7000L/PM720L1030 /PM720L2004 1. 2. 3. STEPS FOR CONVERSION IDENTIFY AND REMOVE BURNER CONTROLLER AND LIMITS CIRCUIT WIRE FROM TERMINAL NO.
SECTION V 1. 2. 3. 4. 5. 6. 7, REPLACING R4150 MODELS WITH 13- OR 15-TERMINAL SUBBASES Disconnect all power to programmer. Remove R4150 from subbase (trade-in to Authorized Distributor). Mark all wires on subbase; i.e., wires connected to terminal “9” should be marked “9”.
E1229A CONVERSION FOR R4150A, B, AND C MODELS 120 VOLT ONLY USE BC7000L/PM720M2002.
E1230A CONVERSION FOR R4150G1004, G1020, G1046, G1103, G1111, G1145, G1178 MODELS 120 VOLT ONLY USE BC7000L/PM720G2013.
E1231A CONVERSION FOR R4150G1012 AND G1079 MODELS 120 VOLT ONLY USE BC7000L/PM720M2002.
E1232A CONVERSION FOR R4150M USE BC7000L/PM720M2002.
An important point after buying a device Honeywell BC7000L1000 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Honeywell BC7000L1000 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Honeywell BC7000L1000 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Honeywell BC7000L1000 you will learn all the available features of the product, as well as information on its operation. The information that you get Honeywell BC7000L1000 will certainly help you make a decision on the purchase.
If you already are a holder of Honeywell BC7000L1000, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Honeywell BC7000L1000.
However, one of the most important roles played by the user manual is to help in solving problems with Honeywell BC7000L1000. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Honeywell BC7000L1000 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center