990 - 1851 C, 10 /2005 User Manual English APC Smart - UPS ® SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack - Mount Uninterruptible Power Supply.
.
1 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brow n outs, sags, and surges from reaching your equipment. The uninterruptible power supply (UPS) filters small uti l- ity line fluctuations and isolates your equipment from large disturbances by internally disconnecting from the utility line.
2 Tower Configuration Note: Illustrations in this document may appear different than the actual h ardware. Œ • Ž • Mount the UPS in a Two - Post Rack Œ • Remove battery bracket screws, battery bracket, and ba t tery.
3 Ž • Note: For information on the four - post rack - mounting kit, see www.apc.com . • Reinstall battery, battery bracket, and screws. ‘.
4 2: S TART UP Connect Equipment to the UPS Rear Panels 110/120 V: 230 V: • Note: A laser printer draws significantly more power than other types of equipment and may ove r load the UPS.
5 Start the UPS 1. Plug the UPS into a two - pole, three - wire, grounded receptacle only. Avoid using exte n sion cords. 110/120 V models : The power cord is attached to the UPS. The input plug is a NEMA 5 - 15P. 230 V models: The power cord is supplied in the UPS literature kit.
6 3: O PERATION Front Display Panel 110/120 V 230 V I NDICATOR D ESCRIPTION On L ine The UPS is supplying utility power to the connected equipment. On Ba t te ry The UPS is supplying battery power to the connected equipment. Ove r load The connected loads are drawing more than the UPS power rating.
7 4: U SER C ONFIGURABLE I TEMS N OTE : S ETTINGS ARE ADJUSTED THROUGH P OWER C HUTE S OFTWARE F UNCTION F ACTORY D E FAULT U SER S E LECTABLE C HOICES D ESCRIPTION Self - Test Every 14 days (336 hour.
8 N OTE : S ETTINGS ARE ADJUSTED THROUGH P OWER C HUTE S OFTWARE F UNCTION F ACTORY D E FAULT U SER S E LECTABLE C HOICES D ESCRIPTION Low Battery War n ing 2 minutes PowerChute B usiness Edition sof t ware provides automatic, una t- tended shutdown when approx i- mately 2 mi n utes of battery ope r- ated runtime r e- mains.
9 5: S TORAGE AND M AINTENANCE Storage Store the UPS covered in a cool, dry location, with th e ba t tery fully charged. At - 15 to +30 ° C (+5 to +86 ° F), charge the UPS ba t tery every six months. At +30 to +45 ° C (+86 to +113 ° F), charge the UPS ba t tery every three months.
10 6: T ROUBLESHOOTING , S HIPPING , AND S ERVICE Use the chart below to solve minor UPS installation and operation problems. Refer to www.apc.com with co m plex UPS problems. P ROBLEM AND / OR P OSSIBLE C AUSE S OLUTION UPS WILL NOT TURN ON UPS not connected to utility power supply.
11 P ROBLEM AND / OR P OSSIBLE C AUSE S OLUTION THE OVERLOAD LED IS ILLUMINATED AND THE UPS EMITS A SU S TAINED ALARM TONE The UPS is overloaded. The connected equipment is dra w- in g more VA than the UPS can sustain. The connected equipment exceeds the specified “maximum load.
12 Shipping and Service Prepare the UPS for shipping: Shutdown and disconnect any equipment attached to the UPS. Shut down th e UPS, and di s connect the UPS from the utility power outlet. Disconnect the battery. If the UPS requires service do not return it to the dealer.
13 7: R EGULATORY AND W ARRANTY I NFORMATION 110/120 V models This equipment has been tested and found to comply with the limits for a Class A digital device, pu r- suant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is opera ted in a commercial enviro n ment.
14 Limited Warranty American Power Conversion (APC) warrants its produc ts to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole o p tion, any such defective products.
An important point after buying a device American Power Conversion Vac 110 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought American Power Conversion Vac 110 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data American Power Conversion Vac 110 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, American Power Conversion Vac 110 you will learn all the available features of the product, as well as information on its operation. The information that you get American Power Conversion Vac 110 will certainly help you make a decision on the purchase.
If you already are a holder of American Power Conversion Vac 110, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime American Power Conversion Vac 110.
However, one of the most important roles played by the user manual is to help in solving problems with American Power Conversion Vac 110. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device American Power Conversion Vac 110 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center