Instruction/ maintenance manual of the product MXA001 American Power Conversion
Go to page of 16
The world's most reliable power protection ® Matrix TM UPS Hard-wire kit accessory MXA001 MXA002 User's Manual American Power Conversion.
Important safety instructions! Please read this manual! V euillez lire ce manuel! Bitte lesen Sie dieses Anleitungshandbuch! ¡Se ruega leer este manual de instrucciones! PLEASE SA VE THIS MANUAL ! It includes important instructions for the safe use and installation of the UPS and its accessories.
Page 1 T able of contents 1.0 Introduction ................................................................................. 2 2.0 Presentation ................................................................................. 3 3. 0 Installation .....
Page 2 1.0 Introduction The hard-wire kit allows the UPS's input and/or output terminals to be permanently secured to building service wiring. This kit is used in place of the power distribution plate and/or input cable plate originally furnished with the UPS.
Page 3 2.0 Presentation Power distribution plate Provides an interface for output hard-wiring of loads. It is used in place of the power distribution plate for cord connected equipment originally furnished with the UPS. Input cable plate Used to replace the input cable plate originally furnished with the UPS.
Page 4 3.0 Installation ■ W arning: Risk of electric shock exists inside the UPS. Input voltage tap selection and power distribution panel replacement should be performed only by qualified service personnel. ■ A vertissement: Un risque de choc électrique existe à lintérieur de lUPS.
Page 5 3.0 Installation T able 3.2.1 Cable Size S tri p Length UP S M ode l Min im um Ma x i m um Input cable Output cable 300 0VA 2. 5 m m 2 12 A W G 1 0 .0 m m 2 8 AW G 12 m m 1/2" 9 m m 3/8" 500 0VA 6. 0 m m 2 10 A W G 1 0 .0 m m 2 8 AW G ■ Cable clamps The UPS is not furnished with cable clamps for strain relief.
Page 6 3.0 Installation Input cable connections 3.3 Input wiring procedure - continued T o remove a knock-out, strike in the area shown with a nail set tool and hammer . Grasp the edge of the knock-out with pliers and twist until the knock-out is separated from the plate.
Page 7 3.0 Installation 3.3 Input wiring procedure - continued 3.3.4 Remove all three input cable wire connections from terminal block labeled L1 , and L2/N . 3.3.5 Remove all screws that secure the input cable plate. Use a pair of wire cutters to remove "tie wraps" binding the input cable to wires inside the Isolation Unit.
Page 8 Unmating of UPS output power connector 3.0 Installation 3.4 Output wiring procedure 3.4.1 Be sure the input circuit breaker is switched off (0) and the input cable is unplugged and/ or has no power applied. Caution: Switching the circuit breaker to off (0) does not remove power to all of the Isolation Unit.
Page 9 Diagram showing power distribution plate earth connection 3.0 Installation 3.4 Output wiring procedure - continued 3.4.4 Use a 3/8" wrench to remove the protective earth wire (green with yellow stripes) ring terminal fastened at the earthing stud on the Isolation Unit.
Page 10 3.0 Installation 3.4 Output wiring procedure - continued 3.4.9 Choose the desired wiring connections from the illustrations on the following pages (Figure 3.4.1 through Figure 3.4.6 ). Insert the stripped wire ends into the appropriate output terminations block terminal and tighten the terminal screws.
Page 11 3.0 Installation 3.4 Output wiring procedure - continued Figure 3.4.1 1 f , 208 V ac loads only 3000 V A model with MXA002 hard- wire kit: 15 Amp maximum. 5000 V A model with MXA001 hard- wire kit: 24 Amp maximum. Figure 3.4.2 1 f , 240 V ac loads only 3000 V A model with MXA002 hard- wire kit: 12.
Page 12 3.0 Installation 3.4 Output wiring procedure - continued Figure 3.4.5 1 f , 120/240 V ac loads ■ ■ ■ ■ ■ 3000 V A model with MXA002 hard- wire kit Each 120 V ac output: 25 Amp maxi- mum. 240 V ac output: 12.5 Amp maximum. T otal output: not to exceed 3000 V A .
Limited W arranty American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products.
Customer Service Note: Before calling the customer service number , please have available your UPS's serial number (see the label at the rear of the UPS).
An important point after buying a device American Power Conversion MXA001 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought American Power Conversion MXA001 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data American Power Conversion MXA001 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, American Power Conversion MXA001 you will learn all the available features of the product, as well as information on its operation. The information that you get American Power Conversion MXA001 will certainly help you make a decision on the purchase.
If you already are a holder of American Power Conversion MXA001, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime American Power Conversion MXA001.
However, one of the most important roles played by the user manual is to help in solving problems with American Power Conversion MXA001. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device American Power Conversion MXA001 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center