Instruction/ maintenance manual of the product APC Silcon 240-320kW 400V American Power Conversion
Go to page of 32
APC Silcon 240-320kW 400V UPS User Guide Copyright ©2000 APC Denmark ApS Information in this document is subject to change without notice and does not represent a commitment on the part of the vendor.
2 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Thank You Thank you for chosing APC Silcon. Please read this User Guide thoroughly prior to installing the system as it provides important information on safe and efficient installation and use.
990-4037 User Guide APC Silcon 240-320kW 400V UPS 3 Contents: 1.0 Introduction 3 1.1 Display Unit 3 2.0 Stop/Start UPS and Operating the External Service Bypass Panel 4 2.1 Stop UPS (for stand-by) 4 2.2 Start UPS (from stand-by) 4 2.3 Stop UPS (for complete power down) 5 2.
4 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Introduction 1.0 Introduction This UPS system is designed to offer reliable and problem-free power supply for several years. The system requires only a minimum of maintenance, but we recommend you follow the maintenance guidelines described in section 6.
Stop/Start UPS and Operating the External Service Bypass 990-4037 User Guide APC Silcon 240-320kW 400V UPS 5 2.0 Stop/Start UPS and Operating the External Service Bypass Panel Only qualified electricians should start up or shut down APC Silcon UPS systems and instructions in the Installation Guide should be followed.
6 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Stop/Start UPS and Operating the External Service Bypass 2.3 Stop UPS (for complete power down) 2.3.
Stop/Start UPS and Operating the External Service Bypass 990-4037 User Guide APC Silcon 240-320kW 400V UPS 7 The UPS is now isolated. Maintenance/repair, disconnection or removal can now be carried out.
8 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Stop/Start UPS and Operating the External Service Bypass 2.4 Start UPS (from complete power down) 2.
Stop/Start UPS and Operating the External Service Bypass 990-4037 User Guide APC Silcon 240-320kW 400V UPS 9 System start-up now completed. NOTICE! One of the following display messages will appear by.
10 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Stop/Start UPS and Operating the External Service Bypass 2.5 Operating the External Service Bypass Switch (single systems) 2.5.1 Bypassing the Single System UPS APC Silcon UPS Mains Load Service Bypass Switch Action 1.
Stop/Start UPS and Operating the External Service Bypass 990-4037 User Guide APC Silcon 240-320kW 400V UPS 11 2.5.2 Switching the Single System UPS from External Bypass into Normal UPS Operation CAUTION! Do not leave UPS out of service for more than 48 hours.
12 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Stop/Start UPS and Operating the External Service Bypass NOTICE! If battery has been disconnected, please refer to section 2.4.1 UPS start-up. Action 1. Set the input s witch (Q001) to position 1 2.
Stop/Start UPS and Operating the External Service Bypass 990-4037 User Guide APC Silcon 240-320kW 400V UPS 13 2.6 Operating the External Service Bypass Switch (parallel systems) 2.
14 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Stop/Start UPS and Operating the External Service Bypass Action Steps 1-4 apply to all the parallel systems. Note that this will switch all systems into bypass operation 1. Press on the ke yboard 2.
Stop/Start UPS and Operating the External Service Bypass 990-4037 User Guide APC Silcon 240-320kW 400V UPS 15 2.6.2 Switching the Parallel System from External Bypass into Normal UPS Operation NOTICE! If battery has been disconnected, please refer to section 2.
16 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Stop/Start UPS and Operating the External Service Bypass Action 1. Check that the output s witch (Q004) is set to position 0 2. Check that all output s witches (Q002) are set to position 1 3. Set input switches (Q001) to position 1 4.
Stop/Start UPS and Operating the External Service Bypass 990-4037 User Guide APC Silcon 240-320kW 400V UPS 17 2.7 Isolating one UPS in a Parallel Configuration for Service/Maintenance 2.7.1 Isolating one UPS in a Parallel/Redundant System In a redundant system one UPS may be isolated for service/maintenance without affecting other parallel UPS(s).
18 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Stop/Start UPS and Operating the External Service Bypass NOTICE! With Q002 in position 0, the UPS can be operated and tested as a single system without affecting the other parallel UPS(s) if correct monitoring device has been installed.
Operation 990-4037 User Guide APC Silcon 240-320kW 400V UPS 19 3.0 Operation The display unit will read parameters, alarms/messages and measured values. LED alarm incorporates audible alarm, indicating unusual operating situations. The keyboard is used to program and control parameters and to display alarm messages and measured values.
20 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Operation 3.2 Display of Measured Values To read measurements, press one or two keys simultaneously as shown below. (Illustrated values are examples only). 3.3 Using the Remote Display The remote display is an inactive unit that is unable to influence the operation of the APC Silcon UPS.
Operation 990-4037 User Guide APC Silcon 240-320kW 400V UPS 21 3.4 Economy Mode When the UPS is running in Economy Mode, the load will be supplied directly from mains and output voltages are UPS monitored. In the event of a mains disruption, the UPS will switch to battery mode without affecting the load.
22 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Parameter Settings 4.0 Parameter Settings Below tables show operating parameters programmable from keyboard.
Parameter Settings 990-4037 User Guide APC Silcon 240-320kW 400V UPS 23 4.1 Programming Keys 4.2 Switching to Bypass Operation Programming Example Scrolls up through list Scrolls down through list Sto.
24 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Parameter Settings To return to normal operation Follow same procedure to program other parameters.
Alarms and Events 990-4037 User Guide APC Silcon 240-320kW 400V UPS 25 5.0 Alarms and Events Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30 seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and if more in the same order as they arise.
26 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Alarms and Events 5.3 Possible Alarms Alarms Description Action 1. Peak current limiter active Peak current limiter activated and UPS switched to bypass operation. System overload Check for blown fuses in installation 2.
Alarms and Events 990-4037 User Guide APC Silcon 240-320kW 400V UPS 27 Alarms Description Action 23. Main inverter failure Temperature of main inverter, too high or inverter fuse blown Check fan, check for airflow obstructions, check for overload, check fuse 24.
28 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Alarms and Events 5.4 Rectifying Alarm Messages Following actions may rectify alarm: • Check local mains supply.
Maintenance & Testing 990-4037 User Guide APC Silcon 240-320kW 400V UPS 29 6.0 Maintenance & Testing UPS maintenance should be carried out by trained service engineers only. Service and maintenance contract is recommended. 6.1 Fan It is recommended to replace fans every 3 years.
30 User Guide APC Silcon 240-320kW 400V UPS 990-4037 Maintenance & Testing If the UPS is to be taken out of operation for an extended period, disconnect the battery in order to prevent discharging. For details, refer to Installation Guide. Action 1.
Warranty 990-4037 User Guide APC Silcon 240-320kW 400V UPS 31 7.0 Warranty 7.1 APC Silcon UPS Limited Factory Warranty APC warrants that the unit, when properly installed and commissioned by APC or AP.
32 User Guide APC Silcon 240-320kW 400V UPS 990-4037 How to Contact APC 8.0 How to Contact APC APC Corporate 132 Fairgrounds Road West Kingston, RI 02892 USA Telephone: 401 789-5735 Fax: 401 789-3710 .
An important point after buying a device American Power Conversion APC Silcon 240-320kW 400V (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought American Power Conversion APC Silcon 240-320kW 400V yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data American Power Conversion APC Silcon 240-320kW 400V - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, American Power Conversion APC Silcon 240-320kW 400V you will learn all the available features of the product, as well as information on its operation. The information that you get American Power Conversion APC Silcon 240-320kW 400V will certainly help you make a decision on the purchase.
If you already are a holder of American Power Conversion APC Silcon 240-320kW 400V, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime American Power Conversion APC Silcon 240-320kW 400V.
However, one of the most important roles played by the user manual is to help in solving problems with American Power Conversion APC Silcon 240-320kW 400V. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device American Power Conversion APC Silcon 240-320kW 400V along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center