Instruction/ maintenance manual of the product GSX Goodman Mfg
Go to page of 56
• Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3.
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit.
PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines.
PRODUCT DESIGN 4 GSX/VSX13 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. Select GSX13 models are available in 208/230 and 460 volt 3-phase applications. These models use R-410A refrigerant.
PRODUCT DESIGN 5 DIMENSIONS W D H M ode l D im en s io n s - W x D x H G S X 1 3 0181A* 26" x 26" x 3 2¼ " G S X 1 3 0241A* 26" x 26" x 3 2¼ " G S X 1 3 0301A* 26".
CONDENSING UNIT SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
CONDENSING UNIT SPECIFICA TIONS 7 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
CONDENSING UNIT SPECIFICA TIONS 8 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
CONDENSING UNIT SPECIFICA TIONS 9 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
CONDENSING UNIT SPECIFICA TIONS 10 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
CONDENSING UNIT SPECIFICA TIONS 11 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
12 COOLING PERFORMANCE DA T A GSX130181A* EXPA NDED PERFORMA NCE DA TA COOLING OPERAT ION MODEL: GSX130181A * / CA* F1824*6** / ZP16K5E-PFV Out door A mbient T emperat ure 65 75 85 95 105 115 Enteri ng In door W et Bul b Temper ature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 77 1 MBh 17.
13 COOLING PERFORMANCE DA T A GSX130181A* E X P A ND ED PE RF ORM A N CE DA T A C OO L IN G OP E RA T ION MOD EL : G S X 13 0181AA / C A* F 1824 * 6* * / Z P 1 6K 5E-P F V O utdoo r Am bi ent Tempe ra.
14 COOLING PERFORMANCE DA T A GSX130241A* EXPA NDED PERF ORMA NCE DA TA COOLIN G OPE RA TION MOD EL: GSX1 30241A * / CA *F18 24*6** / ZP20 K5-PF V Outdoor A mbient T empera ture 65 75 85 95 105 115 Entering Indoor Wet Bul b T empera ture I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 77 15 96 36 77 15 96 36 77 1 MBh 22.
15 COOLING PERFORMANCE DA T A GSX130241A* EX PAN DE D P ER F O R M ANC E D ATA CO O L I NG O PE RAT IO N MOD E L : G S X 130241A A / C A* F 1824 * 6** / Z P 20K 5- P F V O utdoor Am bient Te mpera tur.
16 COOLING PERFORMANCE DA T A GSX130301A* EXPA NDED PERFORMA NCE DA TA COOLING OPE RA TION MODEL: GSX130301 A * / CA *F3030*6** / ZP24K5E-PFV Outdoor A mbient Temperature 65 75 85 95 105 115 Ent erin g I ndoor W et Bu lb T empera ture I D B * A i r f l o w 5 96 3 6 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 1 5 96 36 77 15 96 36 77 1 MBh 27.
17 COOLING PERFORMANCE DA T A GSX130301A* E XP A ND ED PE RF O RM A N CE DA T A COO LING OP E RAT I O N MOD E L : G SX 130301AA / C A * F 3030 * 6** / Z P 24K 5E -P FV O utdoor A mbi e nt T e m pe r a.
18 COOLING PERFORMANCE DA T A GSX130361A* EXPA NDED PERFORMA NCE DA TA COOLING OPE RATION MODE L: GSX13 0361A* / CA *F4860*6* * / ZP31K 5E-PF V Outdoor A mbient Temperature 65 75 85 95 10 5 115 Entering I ndoor W et Bulb Temperature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 77 1 MBh 34.
19 COOLING PERFORMANCE DA T A GSX130361A* EX PAN DE D P ER FO R MANC E D A TA C OOL ING OP ER ATION MOD E L : G S X 130361AA / C A* F4860 * 6* * / Z P 31K 5E -P F V O ut door A m bi e nt T e m pe r a .
20 COOLING PERFORMANCE DA T A GSX130421A* EXPA NDED PERFORMA NCE DA TA COOLING OP ERATIO N MODEL: GSX130421A* / CA *F4860*6 ** / ZP3 4K5-PFV Outdoor A mbient Temperature 65 75 85 95 105 11 5 Entering Indoor W et Bulb Temperature I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 7 7 15 96 36 77 1 MBh 39.
21 COOLING PERFORMANCE DA T A GSX130421A* EX P A N DE D P E R F OR MA NC E DA TA C O OLING OP E R A T IO N MOD EL : G SX130421AA / C A *F4860 *6** / Z P 34K 5- P F V O utd oor Am b i e n t Te m p era .
22 COOLING PERFORMANCE DA T A GSX130481A* EXPA NDE D PERFORMA NCE DA TA COOLING OPE RA TION MOD EL : GSX1 304 8-1 A * / CA *F4860*6 ** / ZP39K 5E -PFV Outdoor A mbient Temperature 65 75 85 95 105 1 15 Entering Indoor W et Bulb Temperature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 77 1 MBh 45.
23 COOLING PERFORMANCE DA T A GSX130481A* EX PA N DE D P ER F O R M ANC E D ATA C OOLING OP E R AT IO N MOD E L : G S X 13 048- 1AA / C A* F 486 0* 6** / ZP 39K5E - P F V O u t d o o r A m bi en t T e.
24 COOLING PERFORMANCE DA T A GSX130601A* EXPA NDED PERFORMA NCE DA TA COOLING OPER A TION MODEL : GSX130 601A * / CA *F4860*6* */ ZP51 K5E -PFV Outdoor Ambient Temperature 65 75 85 95 105 115 Entering I ndoor W et Bulb Tem perature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 77 1 MBh 55.
25 COOLING PERFORMANCE DA T A GSX130601A* E XP A ND E D PE RFO RMA N CE DA T A C OOLIN G OP ER ATION MOD E L : G S X 130601A A / C A* F 4860 * 6** / Z P51K 5E -P FV O utdoor Am bi ent Tempe rat ur e 6.
26 COOLING PERFORMANCE DA T A GSX130181B*/VSX130181A* M O DEL : G S X 1 301 81B * / C A*F1 824 *6B * EX PAN DE D P ER FO R M ANC E D ATA COO L IN G OP E RATION O utdoo r Am bi e n t Te m perat ur e 65.
27 COOLING PERFORMANCE DA T A M O DE L : G SX 1 301 8 1B * / C A*F 1 824 *6B * EX PAN DE D P ER FO R M AN C E D A TA COO L IN G OP E RATION O utdoor Am bie nt Te m pe rat ur e 6 5 7 5 85 9 5 10 5 1 15.
28 COOLING PERFORMANCE DA T A GSX130181C*/VSX130181B* M O DE L : V S X 130 1 81 B* / CA* F1 82 4*6 EX PAN DE D P ER F O R M ANC E D ATA CO OL ING O PERATION O u td o o r Amb i en t T em p er atu r e 6.
29 COOLING PERFORMANCE DA T A MO D EL: VSX13 0 1 8 1 B * / C A * F1 824 *6 EX PAN DE D P ER FO R M AN C E D ATA C O OLING O P E RA TION Ou tdoor Am bi ent Te m pera t ure 65 75 8 5 9 5 105 1 15 E nt eri ng I ndo or We t B ul b Temp e rat ure I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 3 6 77 15 9 6 3 6 77 15 96 3 6 77 15 96 36 77 1 MBh 18.
30 COOLING PERFORMANCE DA T A GSX130241B*/VSX130241A* M O DEL : G S X 1 302 41B * / C A*F1 824 *6B * E XP A ND ED PE RF O RM A N CE DA T A C O OL IN G O P E RATION O utdoor Am bi e nt Te m pera ture 6.
31 COOLING PERFORMANCE DA T A M O DE L: G S X 1 302 41B * / C A*F 1 82 4 * 6B * E X P A ND E D P E RF ORM A N CE DA TA C O OL I NG O P E RATI ON O utdoor Am bi e nt Te m pera t ure 65 75 8 5 9 5 105 1.
32 COOLING PERFORMANCE DA T A GSX130301B*/VSX130301A* M O D E L : GS X 13 0 30 1 B* / CA * F 30 3 0* 6 B* E XP A ND E D PE RF OR M A N CE DA T A CO OL ING O PE RA TION O utdoor Am bi e nt Te m pera tu.
33 COOLING PERFORMANCE DA T A GSX130301B*/VSX130301A* M O D E L : G S X 1 303 01B * / C A*F3 030 *6B * EX PAN DE D P ER F O R M ANC E D AT A CO OLING O P E RA TION O utdoor Am bi e nt Te m pera ture 6.
34 COOLING PERFORMANCE DA T A GSX130361B*/VSX130361A* MO DEL : G S X 1 303 61 B * / C A*F3 036 *6C * E X P A ND E D P E RF ORMA N CE DA T A COO LIN G O P E RAT IO N Ou tdoor Am bient Te mp e rat ure 6.
35 COOLING PERFORMANCE DA T A GSX130361B*/VSX130361A* MO DE L: G S X 1 303 61B * / C A *F3 036 *6C * EX PA N D E D PER FO R MANC E D ATA COO L IN G O P E RAT IO N Out door A m bie nt Te mpe ra t ure 6.
36 COOLING PERFORMANCE DA T A GSX130421B*/VSX130421A* MO DE L : G SX1 304 21B * / C A* F 3 642 * 6C * EX PAN DE D P E R F O R M ANC E D ATA C OOL IN G OP E RA TION Ou t doo r A m bi ent Tempe rat ure .
37 COOLING PERFORMANCE DA T A GSX130421B*/VSX130421A* MO DE L : G /VS X 130 4 2 1B* / CA* F3 64 2*6 C* EX PAN DE D P E R F O R M ANC E D AT A C OOL IN G OP E RA T ION Ou t doo r A m bi ent Tempe rat u.
38 COOLING PERFORMANCE DA T A GSX130481B*/VSX130481A* M O D E L : G S X 1 304 81B * / C A*F 4 860 *6B * EX PAN DE D P ER FO R M AN C E D ATA CO OL ING O PERATION Out door Am bi e nt Te mpe ra t ure 65.
39 COOLING PERFORMANCE DA T A GSX130481B*/VSX130481A* M O D E L : G S X13 0 48 1 B* / CA * F 48 6 0* 6 B* EX PAN DE D P ER FO R M AN C E D ATA C O OL ING O P E RATION O utdoor Am bient Tempera ture 65.
40 COOLING PERFORMANCE DA T A GSX130601B*/VSX130601B* M O DE L : G S X 1 306 01B * / C A *F4 961 *6 A* EX PAN DE D P ER F O R M AN C E D ATA C O OL ING O P E RA TION Out door Am bie nt Te mpe ra tu re.
41 COOLING PERFORMANCE DA T A GSX130601B*/VSX130601B* M O DE L : G SX 1 30 6 01B * / C A*F 4 961 *6 A* EX PAN DE D P ER FO R M ANC E D A TA CO OL ING O P E RA TION Out door Am bie nt Te mpe ra tu re 6.
42 COOLING PERFORMANCE DA T A GSX130363A* MODE L: GSX130 363 A* / C A * F3636 * 6C* E XPANDE D PERF ORM AN CE DATA C OOLIN G OP E R ATION O u td oo r Am bie n t Te m p e r atur e 65 75 85 9 5 105 115 .
43 COOLING PERFORMANCE DA T A GSX130363A* MO D E L: G S X 13 036 3 A * / C A * F36 36* 6 C * EXP AND ED PERFO RMA NC E DA TA COO L ING O PERATION Ou td oo r A mb i e n t Te m p er a tu r e 6 5 7 5 85 .
44 COOLING PERFORMANCE DA T A GSX130483A* MO D EL: G SX130483A* / C A *F4860* 6B* EX PANDED PERFORM ANCE DAT A C OOL I N G OP E R ATIO N O utd oor Am bien t Te m pe r ature 65 75 85 95 105 115 E nte r.
45 COOLING PERFORMANCE DA T A GSX130483A* MO DE L: G S X13 048 3A * / C A * F 48 6 0* 6 B* EX P AND E D PERF O RMA NC E DA T A COOLIN G OPER ATION Out door Ambi ent T emper at ur e 6 5 7 5 85 95 10 5 .
46 COOLING PERFORMANCE DA T A GSX130484A* MO D EL: GSX 130484 A * / C A* F4860* 6B* EX PA NDED PERFOR M ANCE DA TA C O O L IN G O P E R A T IO N O utdo or Am bi e nt Te m pe r ature 65 75 85 95 10 5 1.
47 COOLING PERFORMANCE DA T A GSX130484A* M ODEL: G SX 1 3 04 8 4 A* / CA*F 4 8 60 *6 B* EXP AND ED PE RF O RMA NC E DA T A COO L ING OPERAT ION O ut door Ambi ent T empe r at ur e 6 5 7 5 85 95 10 5 .
48 COOLING PERFORMANCE DA T A GSX130603A* MO D E L: GSX130603 A * / C A * F4961* 6A * E XP ANDED P ERF ORM ANCE D ATA C OO L IN G O P E R AT IO N O utdoo r Am bie nt Te m pe rature 65 75 85 95 105 115.
49 COOLING PERFORMANCE DA T A GSX130603A* M ODEL: GSX 1 3 06 0 3 A* / CA*F4 9 61 *6 A* EX P AND E D P ERF O RM A NC E DA T A COO L ING OPERAT I ON Out door Ambi ent T e mpe r at ure 6 5 7 5 85 95 10 5.
50 COOLING PERFORMANCE DA T A GSX130604A* MO D E L : GSX 130604 A * / C A *F4961* 6A * EXPAND ED PERFOR M AN CE DATA C OOL IN G OP E R AT ION O utdoor Am bi e nt Te m pe r ature 65 75 85 95 1 05 115 E nte r ing I ndoor We t B ulb Te m pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 96 36 77 15 96 36 77 15 96 36 77 1 M Bh 50 .
51 COOLING PERFORMANCE DA T A GSX130604A* M ODEL: GSX1 306 0 4 A* / CA*F4 961 *6 A* EXP A NDED PER F ORMA NC E D A T A CO O L ING OPERATI ON Out door Ambi ent T empe r at ur e 6 5 7 5 85 95 10 5 1 15 .
52 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
WIRING DIAGRAMS 53 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL T IPL E POW ER SOUR CES MA Y BE P RESENT . F A ILURE TO DO SO MA Y CAUS E PROP ERTY DAMAG E, PERSONAL INJURY OR DEA TH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
HI GH V OL T AG E! DISC ONNECT ALL POWE R BEFORE SERVICI NG O R INS T A LLIN G THIS UNIT . MU L T IPL E POW ER SOURCES M A Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAG E, PERSONAL INJURY OR DEA TH . WIRING DIAGRAMS 54 GSX130[18-60]1B*/GSX130181C* VSX130[18-60]1A* US E N.
WIRING DIAGRAMS 55 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL T IPL E POW ER SOUR CES MA Y BE P RESENT . F A ILURE TO DO SO MA Y CAUS E PROP ERTY DAMAG E, PERSONAL INJURY OR DEA TH.
HI GH V OL T AG E! DISC ONNECT ALL POWE R BEFORE SERVICI NG O R INS T A LLIN G THIS UNIT . MU L T IPL E POW ER SOURCES M A Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAG E, PERSONAL INJURY OR DEA TH . WIRING DIAGRAMS 56 Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
An important point after buying a device Goodman Mfg GSX (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Goodman Mfg GSX yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Goodman Mfg GSX - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Goodman Mfg GSX you will learn all the available features of the product, as well as information on its operation. The information that you get Goodman Mfg GSX will certainly help you make a decision on the purchase.
If you already are a holder of Goodman Mfg GSX, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Goodman Mfg GSX.
However, one of the most important roles played by the user manual is to help in solving problems with Goodman Mfg GSX. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Goodman Mfg GSX along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center