Instruction/ maintenance manual of the product GSX Goodman
Go to page of 56
• Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3.
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit.
PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines.
PRODUCT DESIGN 4 GSX13 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet.
PRODUCT DESIGN 5 DIMENSIONS W D H Mod el Dim en sio n s - W x D x H G S X13018 1A * 26" x 26" x 32 ¼" G S X13024 1A * 26" x 26" x 32 ¼" G S X13030 1A * 26" x 26&qu.
CONDENSING UNIT SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
CONDENSING UNIT SPECIFICA TIONS 7 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
CONDENSING UNIT SPECIFICA TIONS 8 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
CONDENSING UNIT SPECIFICA TIONS 9 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
10 COOLING PERFORMANCE DA T A GSX130181A* EXPA NDED PERFORMA NCE DA TA COOLING OP ERA TION MODEL: GSX130181A * / CA* F1824*6** / ZP16K5E-PFV Outd oor A mbie nt T emperat ure 65 75 85 95 105 115 Enteri ng In door W et Bul b Temper ature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 77 1 MBh 17.
11 COOLING PERFORMANCE DA T A GSX130181A* E X P A ND ED PE RF ORM A N CE DA T A C OO L IN G OP E RA T ION MOD EL : G S X 130181 A A / C A* F 1824 *6** / Z P 1 6K 5E - P F V O utdoo r Am bi ent Tempe r.
12 COOLING PERFORMANCE DA T A GSX130241A* EXPA NDED PERF ORMA NCE DA TA COOLIN G OPE RA TION MOD EL: GSX1 30241A * / CA *F18 24*6** / ZP20 K5-PF V Outdoor A mbient T emper ature 65 75 85 95 105 115 Entering Indoor Wet Bul b T empera ture I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 77 15 96 36 77 15 96 36 77 1 MBh 22.
13 COOLING PERFORMANCE DA T A GSX130241A* EX PAN D E D P ER F O R M A N C E D ATA CO OL ING O P E RATION MOD E L : G S X 130241A A / C A* F 1824 * 6 * * / Z P 20K 5- P F V O utdoor Am bi ent Te m pera.
14 COOLING PERFORMANCE DA T A GSX130301A* EXPA NDED PERFORMA NCE DA TA COOLING OPERATION MODEL: GSX130301 A * / CA *F3030*6** / ZP24K5E-PFV Outdoor A mbient Temperature 65 75 85 95 105 115 Ent erin g I ndoor W et Bu lb T empera ture I D B * A i r f l o w 5 96 3 6 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 77 1 MBh 27.
15 COOLING PERFORMANCE DA T A GSX130301A* E XP A ND ED PE RF O RM A N CE DA T A COO L ING O P E RAT ION MOD E L : G S X 130301AA / C A* F 3030 * 6* * / Z P 24K 5E - P F V O utdoor A mb i e nt T e m p .
16 COOLING PERFORMANCE DA T A GSX130361A* EXPA NDED PERFORMA NCE DA TA COOL ING OP ERATION MODE L: GSX13 0361A* / CA *F4860*6* * / ZP31K 5E-PF V Outdo or A m bi ent Temperature 65 75 85 95 10 5 115 Entering I ndoor W et Bulb Temperature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 77 1 MBh 34.
17 COOLING PERFORMANCE DA T A GSX130361A* EX PAN DE D P ER F O R MANC E D ATA C OOL ING OP ER A TION MOD E L : G S X 1303 61AA / C A* F4860 * 6* * / Z P 31K 5E-P F V O utd oor A m bi e nt T e m pe r a.
18 COOLING PERFORMANCE DA T A GSX130421A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OPERATIO N MODEL: GSX130421A* / CA *F4860*6 ** / ZP3 4K5-PFV Outdoor Ambient Te mperature 65 75 85 95 1 05 115 Entering Indoor W et Bulb Temperature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 7 7 15 96 36 77 1 MBh 39.
19 COOLING PERFORMANCE DA T A GSX130421A* EX P A N DE D P E R F OR MA NC E DA TA C O OLING OP E R A T IO N MOD EL : G S X 1 30421AA / C A* F4860 *6** / Z P 34K 5- P FV O utd oor Am b i e n t Te m pera.
20 COOLING PERFORMANCE DA T A GSX130481A* EXPA NDE D PERFORMA NCE DA TA COOLING OPE RA TION MOD EL : GSX1 304 8-1 A * / CA *F4860*6 ** / ZP39K 5E -PFV Outdoor A m bient Temperature 65 75 85 95 105 1 15 Entering Indoor W et Bulb Temperature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 77 1 MBh 45.
21 COOLING PERFORMANCE DA T A GSX130481A* EX PAN D E D P ER F O R M ANC E D ATA C OOLING OP E R AT IO N MOD E L: G S X 13048- 1AA / C A* F 486 0* 6* * / ZP 39K5E -P F V O u t do or A m b i en t T em p.
22 COOLING PERFORMANCE DA T A GSX130601A* EXPA NDED PERFORMA NCE DA TA COOLING OPER A TION MODEL : GSX130 601A * / CA *F4860*6* */ ZP51 K5E -PFV Outdoor Ambient Temperature 65 75 85 95 105 115 Entering I ndoor W et Bulb Tem perature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 77 1 MBh 55.
23 COOLING PERFORMANCE DA T A GSX130601A* E XP A ND E D PE RFO RMA N CE DA T A C OOL IN G OP E R ATION MOD E L : G S X 13060 1A A / C A* F4860 * 6* * / Z P 51K 5E -P FV O utdoor Am bi ent Tempe rat ur.
24 COOLING PERFORMANCE DA T A GSX130181B* M O DE L : G SX1 301 81B * / C A*F1 824 *6B * EX PAN DE D P ER FO R MANC E D A TA COO L IN G OP E RATION O utdoo r Am bi e n t Te m perat ur e 65 75 8 5 95 1 .
25 COOLING PERFORMANCE DA T A M O DE L : G SX 1 301 81B * / C A* F 1 824 * 6B * EX PAN DE D P ER F O R M ANC E D ATA COO L IN G OP E RATION O utdoor Am bie nt Te m pe rat ur e 6 5 7 5 85 9 5 10 5 1 15.
26 COOLING PERFORMANCE DA T A GSX130241B* M O DEL : G SX1 302 41 B * / C A*F1 824 *6 B * E XP A ND ED PE RF OR MA N CE DA T A C O OLING O PERA TION O utdoor Am bi e nt Te m pera ture 65 75 8 5 9 5 105.
27 COOLING PERFORMANCE DA T A M O DE L : G SX1 302 41B * / C A*F 1 824 *6B * E X P A ND ED PE RFO RMA N CE DA T A CO OL ING O P E RATI ON O utdoor Am bi e nt Te m pera t ure 65 75 8 5 9 5 105 1 15 E n.
28 COOLING PERFORMANCE DA T A GSX130301B* M O D E L : GS X 13 0 30 1 B* / CA * F 30 3 0* 6 B* E XP A ND E D PE RF OR M A N CE DA T A CO OLING O P E RA T ION O utdoor Am bi e nt Te m pera ture 65 75 8 .
29 COOLING PERFORMANCE DA T A GSX130301B* M O DE L : G S X 1 303 01B * / C A*F3 030 *6B * EX PAN DE D P ER FO R M ANC E D ATA CO OLING O P E RA T ION O utdoor Am bi e nt Te m pera ture 65 75 8 5 9 5 1.
30 COOLING PERFORMANCE DA T A GSX130361B* MO DEL: G S X1 303 6 1B * / C A *F3 03 6 *6 C * E XP A ND E D P E RF ORM A N CE DA T A COO LIN G O P E RAT IO N Ou tdoor Am bient Te mp e rat ure 65 75 85 9 5.
31 COOLING PERFORMANCE DA T A GSX130361B* MO DEL: G S X 1 303 61B * / C A*F3 036 *6C * EX PAN D E D PER FO R MAN C E D ATA CO O L IN G O P E RAT I O N Out door A m bie nt Te mpe ra t ure 65 75 85 9 5 .
32 COOLING PERFORMANCE DA T A GSX130421B* MO DE L: G SX 1 304 21B * / C A*F 3 642 *6C * EX PAN DE D P ER F O R M ANC E D ATA C OOL IN G OP E RATION Ou t doo r A mb i ent Tempe r at ure 6 5 7 5 85 9 5 .
33 COOLING PERFORMANCE DA T A GSX130421B* MO DE L: G /V S X 130 42 1B* / CA* F 3 64 2 *6 C* EX PAN DE D P ER F O R M ANC E D ATA C OOL IN G OP E RATION Ou t doo r A mb i ent Tempe r ature 6 5 7 5 85 9.
34 COOLING PERFORMANCE DA T A GSX130481B* M O DE L : G SX1 304 81B * / C A*F4 860 *6B * EX PA N DE D P ER FO R M AN C E D A TA CO OL ING O P E RAT ION Out door Am bi e nt Te mpe ra t ure 65 75 8 5 9 5.
35 COOLING PERFORMANCE DA T A GSX130481B* M O D E L : G S X13 0 48 1 B* / CA * F 48 6 0* 6 B* EX PAN DE D P ER F O R M AN C E D ATA CO OLING O P E R AT ION O utdoor Am bient Tempera ture 65 75 8 5 9 5.
36 COOLING PERFORMANCE DA T A GSX130601B* M O DE L : G SX 1 30 6 01B * / C A*F 4 961 * 6A* EX PAN DE D P ER FO R M ANC E D ATA CO OLING O P E R ATION Out door Am bie nt Te mpe ra tu re 65 75 8 5 9 5 1.
37 COOLING PERFORMANCE DA T A GSX130601B* M O DE L : G SX 1 306 0 1B * / C A*F 4 961 *6 A* EX PAN DE D P ER FO R M ANC E D ATA CO OL ING O P E R ATION Out door Am bie nt Te mpe ra tu re 65 75 8 5 9 5 .
38 COOLING PERFORMANCE DA T A GSX130181C* M O DE L : G S X 1 301 81C * / C A*F1 824 * 6** EX PAN DE D P ER FO R MANC E D ATA CO OL I NG O P E RATIO N O utdoor Am bi e n t Te m pera ture 65 75 8 5 9 5 .
39 COOLING PERFORMANCE DA T A GSX130181C* M O DE L : G S X 1 301 81C * / C A*F1 824 *6** EX PAN DE D P ER F O R MANC E D ATA CO OL ING O P E RA T ION O utdoor Am bi e nt Te m pera tur e 65 75 8 5 9 5 .
40 COOLING PERFORMANCE DA T A GSX130181D* MO DEL : GS X 13 018 1D * / CA *F 18 24* 6D* EX P AND E D PE RF ORM A NCE DA T A C OOL ING OP E RA T ION O utdoo r Am bient T e m pera tur e 65 7 5 85 95 105 .
41 COOLING PERFORMANCE DA T A GSX130181 D* M ODE L: GS X 13 018 1D * / CA *F18 24* 6D* EX P AND ED PE RFO RMA NCE DA T A CO O L I N G O P ER AT I O N O ut doo r Am bi e nt T e m pe r a tur e 65 7 5 85.
42 COOLING PERFORMANCE DA T A GSX13024 1 D* M ODE L : GS X 13 024 1D * / CA *F 18 24* 6D* EX P AND ED P E RF ORM A NCE DA T A C OOL ING OP E RA T ION O utd oo r Am bie nt T e m pera tur e 65 7 5 85 95.
43 COOLING PERFORMANCE DA T A GSX1302 4 1D* M ODE L : G S X 13 024 1D * / CA *F 18 24* 6D* EX P AND ED PE RF OR MA NCE DA T A C OOLING OP E RA T ION O utd oo r Am bi e nt T e m peratur e 65 7 5 85 95 .
44 COOLING PERFORMANCE DA T A GSX1303 01DA MO DEL : GS X 13 030 1D * / CA *F 30 30* 6D* EX P AND ED PE RF ORM A NCE DA T A C OOL ING OP E R A TIO N O ut doo r Am bie nt T e m peratur e 65 7 5 85 95 10.
45 COOLING PERFORMANCE DA T A GSX130 3 0 1DA M ODE L : G S X 13 030 1D * / CA * F30 30* 6D* EX P AND ED PE RF O RM A NCE DA T A C OOLING OP E RA TION O utd oo r Am bient T e m pe ra tur e 65 7 5 85 95.
46 COOLING PERFORMANCE DA T A GSX1303 0 1DB M ODE L : GS X 13 030 1D * / CA * F 30 30* 6D* EX P AND ED PE RF ORM A NCE DA T A C OOL ING OPERA T ION O utd oo r Am bie nt T e m pe ra t ur e 65 7 5 85 95.
47 COOLING PERFORMANCE DA T A GSX1303 01DB M ODE L : GS X 13 030 1D * / CA *F 30 30* 6D* EX P AND ED PE RF ORM A NCE DA T A C OOLI NG OPERA T ION O utdo o r Am b i ent T e m p er a ture 65 7 5 8 5 95 .
48 COOLING PERFORMANCE DA T A GSX1303 6 1D* M ODE L : G S X 13 036 1D * / CA * F36 36* 6D* EX P AND ED PE RF O RM A NCE DA T A C OOLING OP E RA TION O utd oo r Am bi e nt T e m pera tu r e 65 7 5 85 9.
49 COOLING PERFORMANCE DA T A GSX1303 61D * M ODE L : G S X 1 3 036 1D * / CA *F 36 36* 6D* EX P AND ED PE RF ORM A NCE D A T A C OOLING OP E R A T ION O utd o o r Ambi ent T e m p er a tur e 65 7 5 8.
50 COOLING PERFORMANCE DA T A GSX1301 8 1E* M ODE L : GS X 13 018 1E * + C AP F18 24B 6D B E XPA N DE D P ER F O R M AN C E D AT A C OOLING OPE RA T ION O utdo o r A mbi ent T e m p er a ture 65 7 5 8.
51 COOLING PERFORMANCE DA T A GSX1301 8 1E* M ODE L : GS X 13 018 1E * + C AP F 18 24B 6 D B EX P AND ED PE RF ORM A NCE DA T A C OOL ING OPERA T ION O utdoo r Am bi ent T e m pe ra tur e 65 7 5 8 5 9.
52 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
WIRING DIAGRAMS 53 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL T IPL E POW ER SOUR CES MA Y BE P RESENT . F A ILURE TO DO SO MA Y CAUS E PROP ERTY DAMAG E, PERSONAL INJURY OR DEA TH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
HI GH V OL T AG E! DISC ONNECT ALL POWE R BEFORE SERVICI NG O R INS T A LLIN G THIS UNIT . MU L T IPL E POW ER SOURCES M A Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAG E, PERSONAL INJURY OR DEA TH . WIRING DIAGRAMS 54 GSX130[18-60]1B* / GSX130181C* / GSX130[18-36]1D* US E N.
WIRING DIAGRAMS 55 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL T IPL E POW ER SOUR CES MA Y BE P RESENT . F A ILURE TO DO SO MA Y CAUS E PROP ERTY DAMAG E, PERSONAL INJURY OR DEA TH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
HI GH V OL T AG E! DISC ONNECT ALL POWE R BEFORE SERVICI NG O R INS T A LLIN G THIS UNIT . MU L T IPL E POW ER SOURCES M A Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAG E, PERSONAL INJURY OR DEA TH . WIRING DIAGRAMS 56 GSX130181 E * US E N.
An important point after buying a device Goodman GSX (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Goodman GSX yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Goodman GSX - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Goodman GSX you will learn all the available features of the product, as well as information on its operation. The information that you get Goodman GSX will certainly help you make a decision on the purchase.
If you already are a holder of Goodman GSX, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Goodman GSX.
However, one of the most important roles played by the user manual is to help in solving problems with Goodman GSX. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Goodman GSX along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center