Instruction/ maintenance manual of the product OG 2697 Generac Power Systems
Go to page of 20
Air -Cooled Generators Distributed Load Center Transfer Switch GENERA TOR INST ALLA TION GUIDELINES OG 2697.
1 Study the SAFETY RULES in the Owner ’ s Manual carefully before installing, operating or servicing any equipment. Use this guide ONL Y in conjunction with the Owner ’ s Manual and Installation Guide shipped with the generator .
2 This exhaust system must be installed properly , in strict compliance with applicable codes and standards. Keep hands, feet, clothing, etc., away from drive belts, fans and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
3 NFP A 101, LIFE SAFETY CODE NFP A 110, ST ANDARD FOR EMERGENCY AND ST ANDBY POWER SYSTEMS NFP A 220, ST ANDARD TYPES OF BUILDING CONSTRUCTION NOTE: It is essential to use the latest version of any standard to ensure that the generator and its accessories comply with all the applicable standards and local codes.
4 Do not open or mutilate the battery . Released electrolyte can be toxic and harmful to the skin and eyes. The battery represents a risk of high short-circuit current. When working on the battery , always remove watches, rings or other metal objects, and only use tools that have insulated handles.
5 Locate the mounting pad as close as possible to the transfer switch and fuel supply . Leave adequate room around the pad for service access (check local code) and place the pad high enough to keep rising water from reaching the generator . Choose an open space that will provide adequate and unobstructed airow .
6 Make sure the lifting equipment you’ll be using has sufcient capacity to safely handle the weight of the generator . Use nylon lifting straps and connect them to the lifting eyes on each corner of the base frame to avoid damaging the enclosure.
7 Check the engine oil, and if necessary , add enough of the recommended oil to bring the level up to the FULL mark on the dipstick. Be careful not to overll the crankcase. The generator was congured for natural gas operation at the factory . Switching over to LP vapor is a simple procedure.
8 Replace the fuel hose and clamp. Then reconnect the wires to the solenoid. Finally , insert the plastic plug that came with the generator into the hole on the bottom of the air cleaner base. Both natural gas and LP vapor are highly volatile substances, so strict adherence to all safety procedures, codes, standards and regulations is essential.
9 When connecting the gas line to the generator , use a short section of UL Listed or AGA- approved exible fuel line in accordance with local regulations.
10 Drill a 1¾ inch hole and feed the conduit through the hole. Remove the knockout in the back of the connection box, feed the wires through the back of the box and secure the conduit with the lock nut. Seal the hole with silicone caulk. Don’t for get to caulk the hole inside the house as well.
1 1 Before beginning any installation, make sure power is shut OFF to the main distribution panel and carefully read the Installation Guide that came with your transfer switch. The distributed load center switch must be mounted close enough to the main distribution panel to accommodate the two-foot, pre-wired conduit.
12 When three-conductor wiring is used, two 120 volt circuits will often share the same neu tral wire. T o avoid overloading the neutral, you should either move BOTH of the circuits that share the neutral or don’t move either of them.
13 Install a 2-pole breaker in the distribution panel to protect the transfer switch. The required Amp rating of the breaker depends on which transfer switch you’re using, so refer to the Installation Guide before purchasing the breaker . Install the breaker in two adjacent empty slots (one above the other) in the main panel.
14 Locate the transfer handle and insert the metal end into the slot in the main contactor assembly . Pull the handle DOWN to move the main contacts to the standby power (generator) position. NEVER OPERA TE THE TRANSFER SWITCH MANUALL Y WHEN LOADS ARE CONNECTED.
15 Use the transfer handle to move the main contacts in the transfer switch to the UP (utility) position. Switch the 2-pole breaker ON in the distribution panel. Now switch the generator ’ s main breaker ON and put the mode switch in AUTO. Shut OFF utility power and make sure the generator starts automatically .
After the engine has completed its cool down cycle and shut down, shut OFF utility power again. When the generator is supplying power to the transfer switch, move the breakers in the switch to the ON position one at a time until the generator has accepted the entire emergency load.
Shut OFF utility power again. The generator should start and the entire emergency load should transfer to the generator . Close the main breaker to restore utility power and allow the engine to cool down and shut itself OFF . W ith the mode switch in AUTO, press the EXERCISER switch.
Notes 18.
Every installation has its own unique set of circumstances and requirements. This booklet provides guidelines for basic installations only and is not intended to cover all applications. If you have any questions or concerns after carefully reading all documentation received with the equipment, contact your local dealer for assistance.
An important point after buying a device Generac Power Systems OG 2697 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Generac Power Systems OG 2697 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Generac Power Systems OG 2697 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Generac Power Systems OG 2697 you will learn all the available features of the product, as well as information on its operation. The information that you get Generac Power Systems OG 2697 will certainly help you make a decision on the purchase.
If you already are a holder of Generac Power Systems OG 2697, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Generac Power Systems OG 2697.
However, one of the most important roles played by the user manual is to help in solving problems with Generac Power Systems OG 2697. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Generac Power Systems OG 2697 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center