Instruction/ maintenance manual of the product DIGITAL ENERGY LP11U GE
Go to page of 48
INSTALLATION / USER MANUAL Digital Energy™ LP 11U Uninterruptible Power Supply 5-6-8-10 kVA GE Digital Energy General Electric Company Te l ephone +41 (0)91 / 850 51 51 CH - 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www. gedigitalenergy.
.
LX: OPM_LPU_11U_5K0_10K_1US_V030 1 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g OPERATING MANUAL Digi tal Energy LP 5/6/8/10-11U UPS LX -D OC Fi le : OPM _LPU_11U_5K0_10K_1US_V030 Manual ver si on 3. 0 So ft wa re ve rs i on R 2.
LX: OPM_LPU_11U_5K0_10K_1US_V030 2 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g CONTENTS 1 IMPORTANT SAFETY INSTRUCTIONS ..................................... 4 1.1 Save these instructions 1.2 General 1.3 Installation 1.
LX: OPM_LPU_11U_5K0_10K_1US_V030 3 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 6 INTERFACING FEATURES ...................................................... 35 6.1 RS232/Contact Interface 6.2 Emergency Shutdown 6.
LX: OPM_LPU_11U_5K0_10K_1US_V030 4 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 1.1 Save these instructions This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
LX: OPM_LPU_11U_5K0_10K_1US_V030 5 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g • It is important that the unit has adequate ventilation. Maintain air movement around and through the unit. Do not block the air vents.
LX: OPM_LPU_11U_5K0_10K_1US_V030 6 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 2.1 Description More than ever before, today's advanced electronic equipment, with complex integrated circuits and other sensitive electronics, needs a stable and continuous AC power supply to operate correctly.
LX: OPM_LPU_11U_5K0_10K_1US_V030 7 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 3.1 The Principles of Operation The UPS stores electric energy in batteries. This allows the UPS to supply output power even when the incoming utility power is cut off completely.
LX: OPM_LPU_11U_5K0_10K_1US_V030 8 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 3.4 Automatic Bypass Switch If the output converter is unable to deliver the demanded output power because of overload or overtemperature, the automatic bypass switch will automatically transfer the load to the utility.
LX: OPM_LPU_11U_5K0_10K_1US_V030 9 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 4.1 Transport NOTE: Transport the UPS only in upright position. Check for sufficient floor and elevation loading capacity. Move the UPS in its original package to the final destination room.
LX: OPM_LPU_11U_5K0_10K_1US_V030 10 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g • Ensure that the total power requirement of the equipment to be protected does not exceed the rated output power of the UPS.
LX: OPM_LPU_11U_5K0_10K_1US_V030 11 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 4.5.1 Installation Procedures 4.5.1.1 Standard installation procedure: input voltage 208-240Vac, output voltage 120/208/220/230/240Vac.
LX: OPM_LPU_11U_5K0_10K_1US_V030 12 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 4.5.1.2 Installation procedure: input voltage 120Vac (optional, 5-6kVA only ), output voltage 120/208/220/230/240Vac. If a battery extension pack is to be installed, please proceed with section 4.
LX: OPM_LPU_11U_5K0_10K_1US_V030 13 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 4.5.2 Available input voltages: hardware modifications The following input voltages are possible: 208, 240 Vac (see 4.5.2.1) and 120 Vac (see 4.
LX: OPM_LPU_11U_5K0_10K_1US_V030 14 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 4.5.2.2 Input voltage 120Vac (optional, 5/6kVA only ). LP-U UPS equipped with an (optional) step-up transformer (5/6kVA models only) can be connected to an input voltage of 120Vac.
LX: OPM_LPU_11U_5K0_10K_1US_V030 15 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g Output tap changed to 240 Volt (p ark ) (p ark ) ( connect ) (p ark ) (p ark ) ( connect ) Output tap factory setting: 208 Volt 4.
LX: OPM_LPU_11U_5K0_10K_1US_V030 16 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 4.5.3.3 Output voltage 220/230/240Vac 1. The factory setting of the output tap (208Vac) has to be changed to 240Vac. Follow the procedure as described in section 4.
LX: OPM_LPU_11U_5K0_10K_1US_V030 17 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g For LP 8/10kVA: 8. Remove all links between the terminals. 9. Split both the load wires and spread one wire over terminal 1-2 and the other over 3-4 respectively.
LX: OPM_LPU_11U_5K0_10K_1US_V030 18 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 4.5.5 Installation of GE Digit al Ener gy ™ LP-U battery extension pack(s) The numbers between (brackets) refer to figures 19-21 in section 5.
LX: OPM_LPU_11U_5K0_10K_1US_V030 19 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 4.5.6 LP 11U series: 2 / 3 / 4 parallel operating units – additional info The RPA option (Redundant Parallel Architecture) allows you to create a redundant UPS system in which 2, 3 or 4 LP-U units operate in parallel.
LX: OPM_LPU_11U_5K0_10K_1US_V030 20 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 5. The right option slot (14) at the rear of the unit contains the the RPA-card. Before the parallel system can be put into operation a unique number has to be appointed to each UPS in the system.
LX: OPM_LPU_11U_5K0_10K_1US_V030 21 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 4.5.6.3 Notes concerning use / maintenance of a parallel system ECO-mode: If LP-U units operate in parallel, the ECO-mode feature is not available.
LX: OPM_LPU_11U_5K0_10K_1US_V030 22 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 5.1 Description of Front and Rear Panel 1 LCD screen 2x16 characters, shows UPS system data, status messages, settings. The language is selectable: English, German, French, Italian, Spanish.
LX: OPM_LPU_11U_5K0_10K_1US_V030 23 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g Rear panel of the step-up transformer: 11b Input terminals L, N and GND 17 .
LX: OPM_LPU_11U_5K0_10K_1US_V030 24 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 5.2 Start-up The numbers between (brackets) refer to figure 19 in section 5.
LX: OPM_LPU_11U_5K0_10K_1US_V030 25 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 5.3 Use Once the unit is in operation, there is no need to switch the unit on/off during use.
LX: OPM_LPU_11U_5K0_10K_1US_V030 26 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 5.3.2 Status and Alarm Menu The UPS alerts the user with a standard alarm screen that the operating mode has changed and/or that an alarm situation occurs: The actual operating mode, the possible modes are mentioned below.
LX: OPM_LPU_11U_5K0_10K_1US_V030 27 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g LOADnotPROTECTED BATTERY DEPLETED LOADnotPROTECTED BATTERY LOW UPS SHUTDOWN LEFT 2 MINUTES BYPASS ERROR FUSE FAILURE After 24 hours of charging time, the battery voltage did not reach the normal float voltage.
LX: OPM_LPU_11U_5K0_10K_1US_V030 28 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g The output converter frequency is not synchronized to the utility (input) frequency.
LX: OPM_LPU_11U_5K0_10K_1US_V030 29 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g Service information on internal timer. Frequency tracking range: output converter frequency will follow the bypass frequency within these limits before returning to its own internal frequency.
LX: OPM_LPU_11U_5K0_10K_1US_V030 30 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 5.3.4 Set-up Menu To enter the set-up menu: 1. Be sure the UPS is switched off. 2. Press push-button 'Enter/Reset' (front panel) and then turn switch ‘UPS on/off’ (rear panel) into position ‘on’ (up).
LX: OPM_LPU_11U_5K0_10K_1US_V030 31 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g Controls functioning of the automatic bypass switch. Range: ENABLED/DISABLED. If the UPS is used as a frequency converter you may change the setting to ‘DISABLED’.
LX: OPM_LPU_11U_5K0_10K_1US_V030 32 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 5.4.3 Deep Battery Test The runtime as shown on the LCD screen is calculated, and the value is initially based on the capacity of new batteries.
LX: OPM_LPU_11U_5K0_10K_1US_V030 33 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 5.5 Other Features 5.5.1 Shutdow n 'Remote shutdown' : Using communication capabilities, the computer can direct the UPS to turn itself off following controlled shutdown of the system.
LX: OPM_LPU_11U_5K0_10K_1US_V030 34 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 5.5.5 ECO-mode The UPS is equipped with the ‘ECO-mode’ feature. If the feature is enabled, the load is operated on utility through the electronic bypass switch.
LX: OPM_LPU_11U_5K0_10K_1US_V030 35 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g The UPS is equipped with 3 ‘option slots’ (rear panel, 12-14). In the most left slot (12) an RS232/contact interface card is factory installed.
LX: OPM_LPU_11U_5K0_10K_1US_V030 36 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 7.1 Extended Runtime Extended runtime versions are equipped with additional separate battery packs to increase the runtime of the unit.
LX: OPM_LPU_11U_5K0_10K_1US_V030 37 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 7.4 PDM: Power Distribution Module This Power Distribution Module (PDM) contains 4 x Nema 5-20R, 2 x Nema L6-30R and 1 x Nema L14-30 R Power sockets (see fig.
LX: OPM_LPU_11U_5K0_10K_1US_V030 38 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g 8.1 General When used properly, the UPS is virtually maintenance free other than keeping the air inlets/outlets free from dust.
LX: OPM_LPU_11U_5K0_10K_1US_V030 39 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or load) to determine whether the problem is caused by the unit itself or by its environment.
LX: OPM_LPU_11U_5K0_10K_1US_V030 40 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g UPS Type : 5-11U 6-11U 8-11U 10-11U Output power (kVA/kW) : 5/4 6/4.
LX: OPM_LPU_11U_5K0_10K_1US_V030 41 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g UPS Type : 5-11U 6-11U 8-11U 10-11U AU TOMA TIC BYPASS SWITCH The automatic switch provides transfer of the load to the utility voltage w ithout any interruption of the supply.
LX: OPM_LPU_11U_5K0_10K_1US_V030 42 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g UPS Type : 5-11U 6-11U 8-11U 10-11U ENCLOSURE Sheet steel cubicle : VSD2 VS.
LX: OPM_LPU_11U_5K0_10K_1US_V030 43 GE DE LP 11U UPS: Installation / User Manual 3.0 (US) Digital En e rg y ™ LP Serie s g Dimensions Conduit Box Center of Gravity UPS cabinet, dimensions hxwxd: 680 x 310 x 710 mm 26.8 x 12.3 x 28.7 inch Center of gravity, position : H = 275 mm / 10.
Digital Energy ™ LP Serie s g LP 5/6/8/10-11U installation drawings Model Heat dissipation Linear load 240 Volt Dimensions Air flow 100% load Rel. humidity non-cond. Altitude (max 4000m) Input wiring Output wiring 100% load 50% load h w d Weight Amb.
Digital Energy ™ LP Serie s g LP 5/6/8/10-11U 208-240V input d h w CASTORS NORMAL: POSITION 1 (LOAD ON UPS) SERVICE: POSITION 2 (LOAD ON BYPASS) MANUAL BYPASS SWITCH INPUT/OU TPUT TERMIN ALS EARTH C.
Digital Energy ™ LP Serie s g LP 5/6-11U 120V input d CASTORS NORMAL: POSITION 1 (LOAD ON UPS) SERVICE: POSITION 2 (LOAD ON BYPASS) MANUAL BYPASS SWITCH INPUT/OU TPUT EARTH CONNECTION IS ESSENTIAL I.
An important point after buying a device GE DIGITAL ENERGY LP11U (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought GE DIGITAL ENERGY LP11U yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data GE DIGITAL ENERGY LP11U - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, GE DIGITAL ENERGY LP11U you will learn all the available features of the product, as well as information on its operation. The information that you get GE DIGITAL ENERGY LP11U will certainly help you make a decision on the purchase.
If you already are a holder of GE DIGITAL ENERGY LP11U, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime GE DIGITAL ENERGY LP11U.
However, one of the most important roles played by the user manual is to help in solving problems with GE DIGITAL ENERGY LP11U. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device GE DIGITAL ENERGY LP11U along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center