Instruction/ maintenance manual of the product SG3K-2TX Falcon
Go to page of 26
OWNER'S OPERA TING MANUAL Uninterruptible Power Supply Models: SG800-1, SG800-2 SG1K-1T , SG1K-2T SG2K-1T , SG2K-2T , SG2K-2TXI SG3K-1T , SG3K-2T , SG3K-2TX Det ailed SG Series product specifications are available in PDF format at www .falconup s.
SG UPS Features. ...... 1 SG Series Online UPS Block Diagram. .... 1 Import ant Safety Instructions (READ FIRST) .... 2 Chapter 1. SG Series UPS Overview ..... 3 T rue Regenerative Online Design .... 3 Input Power Factor Correction .... 3 Microprocessor Control .
SG SERIES UPS FEA TURES SG SERIES ON-LINE UPS SYSTEM BLOCK DIAGRAM T rue Double Conversion On-Line Design Input Power Factor Correction Wide Input V oltage W indow Pure Sinewave Output Precision Outpu.
IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS This manual contains import ant instructions which must be followed during the installation, operation and maintenance of this UPS and its batteries. Please read all instructions before operating this equipment and save this manual for future reference.
CHAPTER CHAPTER 1 1 SG Series UPS - Overview T rue Regenerative On-Line Design As new and innovative technologies have become the backbone of today's businesses, maxi- mum system availability is critical and downtime is more expensive than ever .
CHAPTER CHAPTER 2 2 INST ALLA TION INSTRUCTIONS 1. V erify the following is included in the UPS shipping carton: (1) UPS, (1) Software Diskette(s) & Manual, (1) Power Cord (800V A-1KV A models only), (1) Owners Manual & (1) UPS/Computer Cable.
5. For SG800 - SG1K models, connect the power cord to the UPS inlet located on the UPS rear panel. On SG1.5K - SG3K models the line cord is permanently att ached to the UPS. 6. Select a suitable location for the UPS near enough to the computer or equipment to to be protected.
DIP SWITCHES SELECTION TABLE ON = 1 OFF = 0 SW2 SW1 VOLTAGE Down Down 100V Down Up 110V Up Down 120V (Factory default) Up Up 115V SW2 SW1 VOLTAGE Down Down 220V Down Up 230V (Factory Default) Up Down .
TYPICAL EXTENDED BA TTER Y BANK & UPS INTERCONNECTION (Mini-tower models shown; same applies for floor st anding banks) INST ALLA TION PROCEDURE FOR EXTENDED BA TTERY BANKS 1. Remove the battery fuse located on the UPS rear panel. See illustration above.
BATTER Y OP TION MODEL S W/O C h a r ger SGB2S7-1K3 SGB4S7-1K3 SGB5S7-1K3 SG B10S7-1K 6 SG B10S7-1K 6 BATTER IES 6 Piece s 12V, 7AH 12 Piece s 12V, 7AH 15 Piece s 12V, 7AH 30 Piece s 12V, 7AH 60 Piece s 12V, 7AH BATTER IES IN UPS 3 each of 12V, 7A H # of CASES In c h e s (mm) 1 Mini-To w er 13.
9 CHAPTER CHAPTER 3 3 OPERA TION 1 2 3 4 5 6 7 8 9 10 11 UPS FRONT P ANEL INDICA TOR AND FUNCTION KEYS 1. LOAD LEVEL INDICA T OR LEDS *The first or bottom LED is lit when the output load is greater than 25% of the rated output of the UPS. *The second LED is lit when the output load is greater than 50% of the rated output of the UPS.
5. BYP ASS INDICA T OR LED When this LED is lit the UPS bypass is active. Should the Alarm LED be lit at the same time, the UPS detected an internal failure and the UPS must be serviced. 6. INVERTER INDICA T OR LED When this LED is lit, the UPS inverter is operating and powering the connected load.
AUDIBLE ALARMS Audible alarm signals are divided into two different levels of alarm st atus. Category one alarms represent normal or correctable operational alarms. Category two alarms are sounded in the event of abnormal operation. 1. Category one alarms : a.
OPTIONAL EXTERNAL BATTERY CONNECTOR OUTPUT RECEPTACLES (6 places without ex t ernal batter y option, 4 plac es as shown) COVER PLATE FOR OPTIONAL DIP SWITCHES RS- 232 CONNECTOR COOLING FAN DO NOT BLOC.
COVER PLATE FOR OPTIONAL SNMP AGENT DIP SWITCHES RS-232 CONNECTOR COOLING FANS DO NO BLOCK MAIN POWER SW ITCH & INPUT CIRCUIT BREA KER INPUT LINE CORD OUTPUT FUSE S (2 pl aces) OPUTPUT RECEPTACLES (6) NEMA 5 -15R STANDARD EXTERNAL BATTERY CONNECTOR COVER PLATE OTHER OUT PUT RECEPTACLE CONFIGURATIONS ARE AVAILABLE.
14 SG2K-2TXI & SG3K-2TX T ypical Rear Panel Overview COVER PLAT E FOR COMMUNICATIONS SLOT EX TE R NAL BA TTERY CONNECTOR COVER PLATE OUT PUT FUSES FO R THE TOP R ECE P T AC LE 208- 240V ac OUTPU T.
CHAPTER CHAPTER 5 5 COMMUNICA TIONS INTERF ACES RS-232 INTERF ACE 15 P in # Function explan ation I/O 9 RS 232 Rx INP UT 6 RS 232 Tx OUT PUT 7 Gr ound Location: The RS-232 interface is standard on all SG series UPS models. The port is located on the UPS rear panel, via a DB-9 female connector .
16 DR Y CONT ACT & OPTO COUPLER INTERF ACE BOARD OPTIONS JP1 JP2 JP3 J1 J2 J3 DB- 9 T ypical Falcon Dry Contact Relay Board PIN DESCRI PTION 1 Low Battery ( When UPS reaches low battery, c ontact acti vat es) (J1, 1-2 short = N.O) (J1, 2-3 short = N.
17 PIN ASSIGNMENT FOR THE F ALCON UA88373 OPTO-COUPLER OPTION BOARD (no-byp ass signal) PIN DESCRI PTIO N 1 Not Used 2 Uti lity Los s ( N.O.) ( C l os es upon ut i li t y loss) 3 Utili t y Loss (N.C.) ( O pens upon util it y loss) 4 Comm on for pins 2, 3 & 5 5 Lo w Batte ry (N .
APC Style Dry Cont act Relay Board PIN DESCRIPTION 1 Remote Shutdown (on battery operation only) 2 Remote Shut down Common 3 Not Used 4 Low Ba ttery Co m mon 5 Low Ba tte ry ( N .
CHAPTER CHAPTER 6 6 Maintenance & T echnical Support 1. Care & Maintenance Falcon ® SG Series UPSs are designed to be maintenance-free. They can be cleaned with a damp cloth or non-abrasive cleanser , providing the UPS is turned off and the input plug is disconnected from the utility source.
The following precautions should be observed by a qualified technician when working with batteries. 1. Remove watches, rings, or other met al objects. 2. Use tools with insulated handles. 3. W ear rubber gloves and boots. 4. Do not lay tools or met al parts on top of batteries.
6. T echnical Support Y our F ALCON ® Electric SG Series UPS is backed by one of the finest customer service teams assembled. Write, call, fax or email should you require technical assistance or service. Falcon Electric Inc. 5106 Azusa Canyon Road Irwindale, CA.
GENERAL PROVISIONS F ALCON® ELECTRIC INC., hereby warrants product shipped under this agreement to be free from defective workmanship for a period of two years following date of shipment. This Limited New Product W arranty Agreement only applies to covered repairs to the product occurring within the United S tates and Canada.
SG Series TM UPS PLUS ® 800VA to 1.5kVA Model Number SG800 -1T SG1K -1T SG1K - 2T SG1.5K -1T Nominal VA 800 1000 1000 1500 Electrical I nput Nominal AC Voltage 120V 120V 230V 120V AC Voltage Range 87- 140V 87-140V 170 -275V 87- 140V Current - Amps 5.
SG Series TM UPS PLUS ® 2kVA & 3kVA Electrical Input Nominal AC Voltage 120V 230V 120V 230V 230V AC Voltage Range 87 – 140V 170 – 275V 87 – 140V 170 – 275V 170 – 275V Current – Amps 14.2 7.4 21.4 11.2 7.5 11.3 Frequency 50/60 Hz ± 5% (Auto – Tracking) Power Factor Correction > 0.
An important point after buying a device Falcon SG3K-2TX (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Falcon SG3K-2TX yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Falcon SG3K-2TX - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Falcon SG3K-2TX you will learn all the available features of the product, as well as information on its operation. The information that you get Falcon SG3K-2TX will certainly help you make a decision on the purchase.
If you already are a holder of Falcon SG3K-2TX, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Falcon SG3K-2TX.
However, one of the most important roles played by the user manual is to help in solving problems with Falcon SG3K-2TX. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Falcon SG3K-2TX along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center