Instruction/ maintenance manual of the product GXT2-10000RT208 Emerson
Go to page of 56
AC P ow er For Business-Criti cal C on tinuity™ Li eber t ® GX T2-10000R T208 ™ Us er Man ual–10kV A, 60 Hz, 120/208/240V.
.
i T ABLE OF CONTENTS I MPORT ANT S AFETY I NSTRUC TIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii 8.3 Configuration Program—Installa tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 8.4 Establishing Communica tion Link with the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 8.
iii 11 . 0 C OMMU NICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 11.1 Communications Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iv FIGURES Figure 1 10 kVA Dual Inverter Liebert GXT2-100 00RT208, fron t and rear views . . . . . . . . . . . . . . . . . . . . 7 Figure 2 Internal batte ry pack and connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 I MPORT ANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual co ntains important safe ty instructions . Read all safe ty, installation an d operating instructions befo re operating th e Uninterruptible P o wer System (UPS). Adhere to all warn ings on the unit and in this manual.
2 When replacing batteries, replace with the same Li ebert authorized replacement battery kits. When replacing the power module, replace it with the sa me Liebert authorized replacement power module kit. ! CAUTION Do not dispose of battery or batterie s in a fire.
Glossary of Symbols 3 1.0 G LOSSARY OF S YMBOLS Risk of ele ctrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the .
Introduction and System Descriptio n 4 2.0 I NTRODUCTION AND S YSTEM D ESCRIPTION Congratulations on your choice of the Liebert G XT2-10000RT20 8 Uninterruptible Power Supply (UPS). It provides conditioned power to microcomp uters and other sens itive electronic equipment.
System Description 5 3.0 S YSTEM D ESCRIPTION 3.1 T ransient V olt age Surge Suppr ession (TVSS) and EMI/RFI Filters These UPS components provide surge protection and filter both elect romagnetic interference (EMI) and radio frequency interference (RFI ).
System Description 6 3.5 DC to DC Converter The DC-to-DC converter utilizes energy from the batte ry system and rai ses the DC volta ge to the opti- mum operating voltage for the inverte r. This allows the inverter to operate co ntinuously at its opti- mum efficiency and volt age, thus increasin g reliability.
Major Compo nents 7 4.0 M AJOR C OMPONENT S The Liebert GXT2-10000RT208 is composed of thre e major assemblies to pr ovide easier handling, installation and versat ility. 4.1 Main Frame and Electronics This 6U cabinet arrive s without internal batteries to lighten the UPS for easier instal lation.
Major Compo nents 8 4.3 Input/Output T erminal Blo cks a nd Optional Output Distribution The UPS is shipped with hardwire terminal blocks. For maximum flexibility, additiona l distribution options are available that provide the be nefit of output receptacle convenience.
What’ s Included 9 5.0 W HAT ’ S I NCLUDED The Liebert GXT2-10000RT208 is shipped with these items: • UPS user manual • Vertical display overlay • Front bezels - 3 • Top bezels - 3 • Bat.
Installation and Configurat ion 10 6.0 I NST ALLATION AND C ONFIGURATION This section includes instructions on how to install, configur e and pe rform initial electrical checks of your UPS installation. DO NOT attempt to start the UPS, turn on any circuit breaker or energize the inp ut power until instructed to do so in 7.
Installation and Configurat ion 11 6.1.2 Inst alling the Adjust able Rack-Mount Kit—Sold Sep arately This kit contains pa rts needed to mount several di fferent models o f UPS an d external battery cabi- nets into EIA310-D standard four- post racks that are 18-32 " deep (457-813mm).
Installation and Configurat ion 12 4. Ge t eight (8) M4 screws a nd eight (8) M4 nuts from the hardware pack in this kit. Each nut has a locking, nylon insert that begins gripping the screw when it is halfway tight. Make sure to tighten the nut and screw completely to ensure locking action.
Installation and Configurat ion 13 6.2 External Battery Cabinet Inst allation Optional Liebert external battery cabinets may be connec ted to the UPS to prov ide additional battery run time. External battery cabinets are design ed to be placed on one side of the UPS or stacked beneath the UPS.
Installation and Configurat ion 14 6.3 Connect Input/Output Power The UPS has hardwire terminal bloc ks for input and output electrical connections. Optional output distribution modules permit connecting additi onal loads to the UPS. These optional plug-a nd-play distribution modules offer di fferent ty pes and numbers of connection plugs.
Installation and Configurat ion 15 6.3.2 Input & Output T erminal Block Connections Conduit entry holes are provided on the rear and side of the box. Input and ou tput wiring should not share the same conduit. For best performance, distribute all L-N loads evenly between L1 and L2.
Installation and Configurat ion 16 6.3.3 Add an Output Power Distribution Module—Op tional To add an o ptional output distrib ution module to the Liebert GXT2 10000RT208: 1. Remove the four screws securing the blank out put distribution cover plate to the rear of the UPS.
Installation and Configurat ion 17 6.4 Inst all the Internal Battery Packs To facilitate ship ping and insta l lation, the Liebert GXT2-10000RT2 08 ships without the internal bat- tery packs installed. Once the UPS is installed in place, the internal battery packs must be installed.
Initial St artup and Electric al Checks 18 7.0 I NITIAL S T ARTUP AND E LECTRICAL C HECKS Initial Startup and the Configuration Program —The UPS ships with a default 120 VAC L-N setting. This is also the most robu st setting in that it can operate with either input phase angle (120 or 180 degrees).
Initial St artup and Electric al Checks 19 18. Press the On button for one seco nd. The bypass indicator will li gh t for several seconds before the UPS On indicator turns on continuously. If th e batteries are charged above 90% of capacity, automatic battery test will run for about 15 seconds.
Configuration Prog ram 20 8.0 C ONFIGURATION P ROGRAM The final step of in stallation may require custom conf iguration of your U PS using the en closed config- uration program. Some configuratio n setti ngs may be changed onl y whil e the UPS is off.
Configuration Prog ram 21 8.3 Configuration Program—Inst allation An easy-to-use installation progra m streamlines th e installation of the configuration program. If you have a previous version of this configuration program installe d, Liebert recommends uni nstalling it by using its Uninsta ll program before installing this updated version.
Configuration Prog ram 22 If this message i s displayed che ck the follow ing items: • Verify that the serial communicati on cable is connected properly.
Configuration Prog ram 23 8.5.4 On-Screen Reminders As pending ch anges are selecte d, on-screen messages will remind the user if the UPS may be On, or must be Off, for the setting to be pro- grammed once the Apply or OK bu tton is pressed. If there are no changes, these mes- sages are shaded.
Configuration Prog ram 24 8.6 UPS T ab When the program starts, the foll owing window will open displayi ng the UPS model along with the current UPS settings.
Configuration Prog ram 25 8.6.3 Frequency Selection The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the model. All models are capabl e of being used as 50 Hz or 60Hz systems. The UPS will Auto-sense th e utility frequency when fi rst plugged in and set the nominal frequency to match.
Configuration Prog ram 26 8.8 Options T a b Used With Earlier Liebert GXT2 Models This version of the configuratio n program will accompany Liebert GXT2 UPS models that support new programming features accessible using the Option s Tab.
Configuration Prog ram 27 8.9 Battery T ab Factory default settings illustrat ed. 8.9.1 Low Battery Time W arning The UPS will estimate remaining op erating time when on batteries. A low battery alarm is activated if the estimated time reaches the Low Battery Time.
Configuration Prog ram 28 8.10 About T ab Version number may be confirmed using the About Tab..
Controls and Indica tors 29 9.0 C ONTROLS AND I NDICATORS Figure 8 Control and indicator overla ys, vertical and horizont al 9.1 ON/Alarm Silence/ Battery T est Button This button controls output powe.
Controls and Indica tors 30 9.3 L1 & L2 Load Level Indicators (T wo Rows of Indicators: 4 Green, 1 Amber) The Load Level indicators disp lay the approximate elec tri cal load placed upon bo th output legs of the UPS at all times. Each indicator represents an approximate 2 5 percent increase in load.
Modes of Operati on 31 10.0 M ODES OF O PERATION 10.1 Normal Mode Operation During normal operation, uti lity power provides energy to the UPS. The fi lters, power fa ctor correction circuit and the inverter process this power to provide computer grade power to connected loads.
Communications 32 11 . 0 C OMMUNICATIONS 1 1.1 Communications Interface Port The Liebert GXT2-10000RT208 UPS has a standard DB-9 serial port female co nnector located on the rear of the UPS un it. Several signals are provided on this p ort and are assigne d as follows: 1 1.
Communications 33 1 1.1.2 Communications—Liebert SNMP/OCWEBCARD SNMP Adapter Attach the larger enclosed fe rrite bead clamp to the network cable, see il lustration at right, u sing the following directions: 1. Open the ferrite bead. 2. Place the netwo rk cable inside the ferrite bead groove.
Communications 34 1 1.4 Remote Emergency Power Off The UPS is equipped with a Remote Emergency Power Off (RE PO) connector. The user must supply a means of interfacing with the REPO circuit to allow d.
Maintenance 35 12.0 M AINTENANCE The Liebert GXT2-10000RT208 requires very little maintenance. The batteries are valve-regulated, non-spillable, flame retardant, lead acid and should be kept charged to obtain their design life. The UPS continuously charges the batteries when connected to the utility supply.
Maintenance 36 12.2 UPS Power Modu le Replacement To remove the UPS power module without s hutting off power to the connected load: 1. Place the UPS on internal bypass. This may be d one by any of th e three follow ing methods: a. Press the Off button on the front panel one time.
Maintenance 37 Figure 10 UPS back p anel—control location Figure 1 1 Power module replacement O utput Breaker 60A 250V~/T Input Breaker 60A 250 V~/T Inver ter Bypa ss I nput Ou tp u t ! U P S ta t i.
Trou bleshooting 38 13.0 T ROUBLESHOOTING The informatio n below indicates va rious symptoms a user may enco unter in the event the Liebert GXT2-10000RT208 develops a problem. Use this in formation to determine whether external factors caused the p roblem and h ow to remedy the situation.
Trou bleshooting 39 Under fault condit ions, the Fault indicators will be illumi nated indefinitely while the bat tery charger is operational, or for a maximum of 5 minute s while the battery charger is not operational. If a problem persists, consult your local dealer, Li ebert representative or contact the Liebert World- wide Support Group.
Trou bleshooting 40 T able 5 T roubleshooting guide Problem Cause Solution UPS fails to start when the ON button is pressed. UPS is short-circuite d or overloaded. Ensure the UPS is OFF. Disconnect all loads and ensure nothing is lodged in output receptacle s.
Trou bleshooting 41 Fault indicato r and diagnostic indicators B and C ar e illuminated. REPO is currently activated. UPS has shut down due to the REPO (Remote Emergency Power Off). The output can not be started by any method. Fault indicato r and diagnostic indicators B and D ar e illuminated.
Trou bleshooting 42 Using the configuration program, the user may specify the number of GX T2-288VBATT external bat- tery cabinets attached to the UPS. The factory default is pr ogrammed for internal batteries only. Table 6 shows estimated run ti mes at different loads.
Trou bleshooting 43 13.1 Auto-Learning Battery Run Times As batteries age, the estimated run times may be come less accurate. The Liebert GXT2-100 00RT208 is programmed to “learn” from a full battery disc harge and modify the esti mated run time for the measured battery capacity.
Specifications 44 14.0 S PECIFICATIONS T able 7 UPS specifications Model Number Liebert GXT2-10000RT208 Model Rating 8000W/8660VA at 127/220 (120 or 240 degrees only) 8000W/8660VA at 120/208 (120 or 2.
Specifications 45 Bypass Protection Limits Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage Re-enable Bypass Operation If input voltage returns to within ±10% of nominal.
Specifications 46 T able 10 Optional output distri bution specif ications—PD-102 Model Number PD-102 DIMENSIONS , W x D x H Shipping, in. (mm) 8.86 x 10.
Specifications 47 14.1 Product W arranty Registration To register for warranty protection: •V i s i t t h e Quick Links section of our Website at: http://www.
Specifications 48.
.
EmersonNetworkPower.com Ensuring The Hi gh Av ai lab ilit y 0f Mission-Critic al Dat a And App lic ations. Emerson Net work P ower , the global leader in enabling business-critical continuity , ensure.
An important point after buying a device Emerson GXT2-10000RT208 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Emerson GXT2-10000RT208 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Emerson GXT2-10000RT208 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Emerson GXT2-10000RT208 you will learn all the available features of the product, as well as information on its operation. The information that you get Emerson GXT2-10000RT208 will certainly help you make a decision on the purchase.
If you already are a holder of Emerson GXT2-10000RT208, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Emerson GXT2-10000RT208.
However, one of the most important roles played by the user manual is to help in solving problems with Emerson GXT2-10000RT208. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Emerson GXT2-10000RT208 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center