(Supersedes PQ404-5) PQ404-6 CHS 161-048642-001 OCTOBER, 1983 4 and Installation, Operation RENEWAL PARTS IDENTIFICATION Horizontal Electric Steam Boiler Model Number CHS 0 – 150 PSI © 2010 Chromalox, Inc. Power CC Size of Output Nominal 90˚C Amps Standard Lbs.
2 High Pressure Control Pressure Gauge Manual Reset Pressure Conrol Electric Control Box Blow Down Drain Valve (L) Return Inlet (J) Heating Elements Step Sequencer (Optional) Wall 30” C B A Wall D I H E Blow Down Drain Valve (L) Check Valve Water Inlet (K) Water Level Control G 60” Safety Valve (G) Steam Outlet (F) INST ALLA TION (cont’d.
3 INST ALLA TION (cont’d.) SPECIAL INSTRUCTIONS FOR CUSTOMERS SUPPL YING THEIR OWN CONDENSA TE OR PUMP SYSTEMS. 1. Check the voltage of the motor before making the wiring connec- tion. Some Chromalox boilers are supplied with dual voltage sys- tems.
4 WIRING (cont’d.) Figure 8 – T ypical Wiring Diagram Power Circuit T erminal Block T o Other Heater Groups To Other Heater Groups T ypical 3 Phase Heater Group To Power Curcuit Relay Step Sequenc.
NOTES 1. Motor , Solenoid V alve and Dotted Control W iring are included if Motor and Pump package is supplied. Solenoid V alve only is sup- plied with 991 17 W ater feed. 2. 1/3 HP Motor is controlled directly without use of Motor Starter . After proper wiring and piping of boiler system is complete, testing of controls can start.
6 RECOMMENDED ST ART -UP PROCEDURES 1. Close globe valve on outlet side of boiler . (Customer Supplied) 2. T urn on boiler and allow pressure to build up to operating pressure. 3. Only open globe valve by quarter turns at first, introducing small- er amounts of steam into process.
7 OPERA TION (cont’d.) Figure 16 – T ypical Wiring for Automatic Blowdown System Now turn the wheel on the large timer until the “of f” tab passes the “time now” arrow . The “boiler normal” light should go out and the valve should begin to open.
8 AUXILIAR Y LOW W A TER CUT -OFF (See page 4 for Wiring Diagram) Operation Operation of this control is accomplished by sensing a minute AC current flowing between submerged contact probe in the boiler shell.
9 5. Connect the ohmmeter between controller terminals W and R and raise the set point of the controller above the actual pressure being measured. The ohmmeter should read the full value of the poten- tiometer measured in step 4 (135 ohms for an L91B).
10 The Sequence Reverser accomplishes its tasks and shows the rela- tive use of each of ten beat stages during the first four days of the cycle. This is how the work load would be distributed on a boiler with- out Sequence Reverser .
11 MAINTENANCE RENEW AL P ARTS IDENTIFICA TION INSTRUCTIONS FOR ELEMENT REPLACEMENT CAUTION: Before installing your new elements, be sure the McDonnell-Miller low-water cut-off is operating perfectly and the float chamber and lower equalizer column are completely clear of sludge or other foreign matter .
2150 N. RULON WHITE BLVD., OGDEN, UT 84404 Phone: 1-800-368-2493 www.chromalox.com RENEW AL P ARTS IDENTIFICA TION (cont’d.) Low Water Cutoff and Water Feed Controls Description Part Number Complete Assembly . . . . . . . . . . . . . . . . . . . . .
An important point after buying a device Chromalox PQ404-6 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Chromalox PQ404-6 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Chromalox PQ404-6 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Chromalox PQ404-6 you will learn all the available features of the product, as well as information on its operation. The information that you get Chromalox PQ404-6 will certainly help you make a decision on the purchase.
If you already are a holder of Chromalox PQ404-6, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Chromalox PQ404-6.
However, one of the most important roles played by the user manual is to help in solving problems with Chromalox PQ404-6. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Chromalox PQ404-6 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center