Instruction/ maintenance manual of the product TP-NAC Carrier
Go to page of 64
Installation Instructions TP-P AC, TP-PHP TP-NAC, TP-NHP P erformance t Series AC / HP Thermostat A07049 A07048 Pr ogrammable Control Non − Pr ogrammable Contr ol Designed and Assembled in the U.S.A. NOTE : Read the entire instruction manual before starting the installation.
.
1 T ABLE OF CONTENTS P AGE SAFETY CONSIDERA TIONS 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INTRODUCTION 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INST ALLA TION CONSIDERA TIONS 3 .
2 INTRODUCTION Carrier ’ s 7 − day , 5/2 − day , 1 − day programmable and non − programmable Performance Series Thermostat Control is a wall − mounted, low − voltage temperature control in either a single unit or a two − piece unit.
3 INST ALLA TION CONSIDERA TIONS Power This control is powered by 24V AC only . It requires 24V AC (Rh and/or Rc and C terminals) of the low − voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections.
4 A07052 Fig. 1 − PCB Br eakout Jumper Models There are programmable and non − programmable models for all applications. They can be configured for AC or HP installations, allowing it to be used in place of all Carrier thermostats. Programmable thermostats may be configured as non − programmable if user desires.
5 dedicated sensor wires may be used for its connection. Details are provided in sensor instructions. Remote Indoor T emperatur e Sensor A remote temperature sensor may be used with the programmable h.
6 Wiring W ire length should be no more than 250 ft (76m). Use 22 A WG for normal wiring applications. Continuous wire lengths over 100 ft (30.5m) should use 20 A WG or larger . INST ALLA TION Carton contains the following components. See Fig. 2 for programmable models or Fig.
7 A07755 Fig. 3 − TP − NAC / TP − NHP Carton Contents 1. Display Module 2. Stand − of f for Equipment Control Module 3. Screws and pig tail 4. Equipment Control Module AC/HP Control Location AC/HP Control should be mounted: Approximately 5 ft (1.
8 AC/HP Control should NOT be mounted: Close to a window , on an outside wall, or next to a door leading to the outside. Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature − radiating objects which could cause a false reading.
9 UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Improper wiring or installation may damage AC/HP Control. Check to make sure wiring is correct before proceeding with installation or turning on power.
10 Tw o − Piece Installation The following steps should be followed for the installation of the two − piece configuration. NOTE : The 2 − wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals.
11 A07226 Fig. 5 − T ake Apart 2. Route wires through lar ge hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be lev- eled for proper operation) and mark wall through 4 mounting holes. T o avoid unintended bending of wall plate plastic, use all 4 screws and an- chors.
12 A07165 Fig. 6 − Backplate Mounting 3. Drill two 3/16 − in. mounting holes in wall where marked. Thermostat may be mounted to a standard junction box, if desired. Hole pattern on ther- mostat mounting base matches junction box mounting holes. 4.
13 Relays OAT RRS SRTN HUM D1 D2 V+ Vg Rc Rh W / W1 G Y/Y2 Y used for single stage cooling C O/W2/B Y1 Y1 used for multi-speed cooling Y1 = stage 1 Y2 = stage 2 Control Module Wiring Guide connect to .
14 A07166 Fig. 8 − Secur e W ir es to T erminal Strip A07167 Fig. 9 − Connect Pigtail W ir es to Display Module.
15 NOTE : The 2 − wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals. Red is V+ Black is Vg 7. Push any excess wire into wall and against mounting base.
16 10. Find suitable indoor mounting location for Equipment Control Module, either near or on equipment. See Fig. 11. IMPOR T ANT NOTE: Equipment Control Module should not be mounted to duct work or below any other contr ols or equipment (i.e. humidistat, humidifier , etc.
17 A07227 Fig. 12 − Standoff NOTE : Standof fs are provided as an aid when installing Equipment Control Module on inside equipment or a solid wall. 12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws.
18 A07218 Fig. 13 − Cover on Equipment Control Module 14. T urn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2 − digit code appears on lar ge display which identifies AC/HP Control configuration.
19 Single − Piece Installation The following steps should be followed for the installation of the single − piece configuration. 1. Remove cover from Equipment Control Module by pressing the two tabs on the bottom edge and pulling away . Route wires through lar ge hole in Equipment Control Module.
20 A07219 Fig. 14 − Equipment Control Module 5. Match and connect equipment wires to proper terminals of each connector block. 6. Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature measurement.
21 A07220 Fig. 15 − Reattach Display Module 9. T urn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2 − digit code appears on lar ge display which identifies AC/HP Control configuration. Refer to Option 33.
22 must be properly set by the installer . (Only those marked with an asterisk * below are available to the homeowner .) The homeowner configurations are described in the owner’ s manual. A special procedure allows entry into the configuration mode.
23 Option 18* — Backlight Configuration Option 19 — Dry Contact (programmable models only) Option 20 — Outdoor Air T emperature Offset Adjustment Option 21* — Keypad Lockout Option 24* — Pro.
24 WHILE IN CONFIGURA TION MODE The option number is displayed in the heat setpoint location and the configuration setting is displayed in the cool setpoint location. On the TP − P AC/PHP (programmable) models, a box will surround the option number .
25 Defaults HP model defaults to HP . AC model defaults to AC. Option 02 — Clean Filter T imer Select hours of blower operation (heating, cooling, or fan) before CHECK FIL TER icon is displayed. With OF selected, icon will never come on, disabling this feature.
26 Sensor 1 Sensor 2 Sensor 3 Sensor 4 RRS SRTN A09130 Fig. 16 − Remote Room Sensor − Parallel W iring This selection determines which sensor the control will use for measuring room air temperature.
27 Option 07 — Zoning This selection should be set to On when the thermostat is to be used as part of a zoning system. It is assumed that the zoning equipment will take care of time guard and cycle timers. The minimum on time is still controlled by the thermostat.
28 C — Reversing valve output (O/W2/B) is energized when COOL mode is selected. Default is C. Option 1 1 — Deadband Setting Between Heat & Cool This option is not available on Heat Only and Cool Only systems. This selection is to allow the installer to choose how much differential exists between the heating and cooling setpoints.
29 On — Auto mode is available. OF — Auto mode is not available. Default is On. Option 16 — Maximum Cycles Per Hour This selection limits the number of cycles per hour that the thermostat allows the system to operate. Selections are 2, 4, 6. 2 — The heating and cooling outputs will be energized no more than 2 times per hour .
30 becomes brighter when a button is pressed. After 10 seconds of no button presses, the backlight will return to the dimmer level until another button press occurs.
31 1 — The user has access to modify setpoints, time of day . 2 — The user has access to change the setpoints only . 3 — The entire keypad is locked. When a button is pressed, the backlight will turn on but none of the operating parameters will be changed.
32 Option 22 — High Cool Latch T emperatur e (only available if outdoor sensor is pr esent) An outdoor sensor is required for high cool latch feature. This selection is only available when Option 1 is set to H2, A2, or h2 and when Option 7 (zoning) is set to OF (off).
33 When a cycle starts under a high heat latch, it will finish the heating cycle on high stage. On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all heating demands.
34 Option 27 — Maximum Heating Setpoint This selection allows the installer to configure the maximum heating setpoint. The range is based on the adjustable deadband value Option 1 1, such that the minimum of the range is 50 F/10 C and the maximum is 90 F/32 C minus the deadband.
35 “overrides” the programmed fan setting by pressing the fan button, the override selection will remain in effect until the next programmed period time.
36 2 — Thermostat will control the W1 and O/W2/B outputs. Default is 1. Option 33 — Single or T wo − Piece Installation This configuration allows the thermostat to compensate for the amount of heat generated by the thermostat electronics to allow more accurate sensing of the temperature sensor .
37 of f even if the user has the fan selection set to continuous fan. The fan output will be turned back on in this temperature range if the maximum capacity of auxiliary heat is on due to system demand (auxiliary heat on in response to a defrost signal shouldn’ t cause the fan to turn back on).
38 SYSTEM ST AR T − UP AND CHECKOUT The AC/HP Control is designed with a built − in installer test capability . It allows easy operation of equipment without delays or setpoint adjustments to force heating or cooling. T o enable installer test mode, press and hold the fan button for 15 seconds.
39 TO TEST F AN Fan button switches F AN icon between AUT O and On. While On is displayed, G output will be ener gized, turning fan on. On some fan coils, fan continues to operate for 90 sec after G signal is removed. Final Settings Be sure to press DONE to exit installer setup mode.
40 The F AN button may be used to select between AUTO (fan on only with equipment) and On (fan on continuously) fan modes. For further information on temperature selection and programming, refer to Homeowner’ s Guide.
41 provides temperature protection for the home in the selected mode, but not comfort. When vacation mode is active, an arrow will be displayed beside “V ACA TION” in the upper left corner of the display . V acation Setpoints A special set of temperature setpoints exist which are active in vacation mode.
42 Te n − Minute Staging Timer In multistage heating or cooling, this timer prevents any higher stage from turning on until preceding stage has been on for 10 minutes. When staging between compressor and electric heat or between compressor and furnace heat, the time is configurable.
43 Thr ee − Minute Minimum on Time In normal operation, when a stage turns on, it will not turn off for a minimum of 3 minutes. If the setpoint is changed, this timer is canceled, allowing the equipment to turn of f immediately when the demand is removed.
44 Pr ogrammable Fan (programmable models only) The fan output can be programmed based on period of the day . When programming for each day and period the fan can be set to On or AUTO.
45 T emperatur e Offset After Power Cycle T o compensate for internal heat build − up from the electronics in the thermostat, the thermostat will add an offset to the actual temperature that it measures. If the thermostat power is cycled quickly , one can witness an immediate increase in the actual temperature displayed due to this added offset.
46 E3 − If AC/HP Control cannot properly read outdoor temperature, and it is needed for proper operation, display will indicate “ −− ” in the outdoor temperature location. E4 − If AC/HP Control’ s internal memory fails, E4 will be displayed.
47 T able 3 – Equipment Configuration Outputs For COOL, HEA T and Emergency Heat modes, the following chart shows the state for each output in each stage of operation EQUIP CONFIG OPTION 01 HARD- W .
48 T able 3 − Equipment Configuration Outputs (cont.) EQUIP CONFIG OPTION 01 HARD- W ARE CONFIG COOL STG 1 COOL STG 2 HEA T STG 1 HEA T STG 2 HEA T STG 3 HEA T STG 4 EM HEA T STG 1 EM HEA T STG 2 2S.
49 WIRING DIAGRAMS Display module Display module wall m ount Equipment Control Module Fan Coil Heat P ump V+ V+ Vg Vg O O V+ V+ RVS/Heat Stage 2 O/B W 2 W3 W2 Vg Vg Heat Stage 1 W /W1 W2 Compressor Y/.
50 WIRING DIAGRAMS(cont.) Therm ostat Fan Coil Heat Pum p OO RVS/Heat Stage 2 O/B W 2 W 3 W 2** Heat Stage 1 W /W1 W 2 Compressor Y/Y 2 Y Y Not Used Y1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooli.
51 WIRING DIAGRAMS(cont.) Therm ostat Fan Coil O RVS/Heat Stage 2 O/B W 2 W 3 Heat Stage 1 W/W 1 W 2 Compressor Y/Y 2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 Aux.
52 WIRING DIAGRAMS(cont.) Therm ostat Fan Coil Air Conditioner O RVS/Heat Stage 2 O/B W2 W 3 Heat Stage 1 W /W 1 W 2 Compressor Y/Y 2 Y Y Not Used Y1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling.
53 WIRING DIAGRAMS(cont.) Therm ostat Fan Coil O RVS/Heat Stage 2 O/B W 2 W 3 Heat Stage 1 W /W1 W2 Compressor Y/Y 2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 Aux.
54 WIRING DIAGRAMS(cont.) Therm ostat Furnace Air Conditioner Heat Stage 1 W /W 1 W/W1 Compressor Y/Y 2 Y/Y2 Y Not Used Y1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Co.
55 WIRING DIAGRAMS(cont.) Therm ostat RVS/Heat Stage 2 O/B W 2 Heat Stage 1 W /W 1 Compressor Y/Y 2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Comm on C C Outdoor A ir Temp OAT Remote Room Sensor RRS OAT/RRS Com OAT /RRS A09158 Fig.
56 WIRING DIAGRAMS(cont.) Therm ostat Furnace Air Conditioner W2 RVS/Heat Stage 2 O/B W 2 Heat Stage 1 W /W 1 W /W1 Compressor Y/Y 2 Y/Y2 Y Not Used Y 1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cool.
57 WIRING DIAGRAMS(cont.) Single-Stage Single-Stage Therm ostat Furnace Air Conditioner RVS/Heat Stage 2 O/B W 2 Heat Stage 1 W /W 1 W/W1 Compressor Low Y1 Compressor High Y/Y 2 Y/Y2 Y Fan G G 24VAC H.
58 THERMOSTA T CONFIGURA TION RECORD Installer _________________________ Model Number ______________________________ Date _________________________ A. Hardware Configuration __________ Seal Hole In W all B.
59 E Configuration Options Option 01 _____ Equipment Type Option 02 _____ Clean Filter Timer Adjustment Option 03* _____ Fahrenheit/Centigrade Selection Option 04 _____ Fan (G) on with W/W1 Selection .
60 E Configuration Options (cont) Option 21* _____ Keypad Lockout Option 22 _____ High Cool Latch T emperature Option 23 _____ High Heat Latch T emperature Option 24* _____ Programmable/Non-Programmab.
.
0 Copyright 2009 Carrier Corp. 7310 W . Morris St. Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 04/09 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
An important point after buying a device Carrier TP-NAC (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Carrier TP-NAC yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Carrier TP-NAC - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Carrier TP-NAC you will learn all the available features of the product, as well as information on its operation. The information that you get Carrier TP-NAC will certainly help you make a decision on the purchase.
If you already are a holder of Carrier TP-NAC, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Carrier TP-NAC.
However, one of the most important roles played by the user manual is to help in solving problems with Carrier TP-NAC. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Carrier TP-NAC along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center