Instruction/ maintenance manual of the product PREMIERLINK 33CSPREMLK Carrier
Go to page of 44
Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificat ions or des igns without notice an d withou t inc urring obligations.
2 Carrier ’ s diagnostic standard tier display tools such as Navigator or Scrolling Marquee can be used with t he Premier- Link controller . A cce ss is available via an RJ-11 connection or a 3-wire connection to the communication bus.
3 PremierLink Contr oller Inputs and Outputs — The PremierLink controller inputs and outputs are shown in T able 1. Contr ol Wiring — The PremierLi nk controller can be connected to either a Carrier-approved therm ostat or CCN compatible tempe rature sensor .
4 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections.
5 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections.
6 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections.
7 RED RED BRN GRN FA N CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections.
8 Table 1 — PremierLink Controller Inputs and Outputs LEGEND INPU TS PO WER TERMINAL (S) SP ACE TEMPERA TU RE (SPT ) AI (10K Ther mistor) J6-7, J6-6 SET POINT ADJUSTMENT (ST O) AI (10K Ther mistor) .
9 Table 2 — Color Code Recommendatio ns Inst all Sens or s ( See Fig. 3-10 ) — The Premi erLink™ controller can be used with ei ther the T 58 Communicating sen- sor or any combination of CO 2 and space tem perature sensors . Refer to the instructions supplied with each sensor for electrical requirements.
10 Table 3 — Thermistor Resista nce vs Temp erature Values for Spa ce Tempera ture Sen sor, Supply Air Temperature Sens or, and Outdoor Air Temperature Sen sor SUPPL Y AIR TEMPE RA T URE (SA T ) SENSOR INST AL- LA T IO N — T he 33ZCSENSA T supply air temperat ure sensor is required for controller operation.
11 Perform the following steps if state or local code requires the use of conduit, or if your installation requires a cable length of more than 8 ft: 1. Secure the probe to the duct with two field-supplie d self- drilling screws. 2. If you are extending cable length beyond 8 ft, use plenum rated, 20 A WG, twisted pair w ire.
12 J6 6 7 RED BLK RED RED BLK BLK BLK RED BLK RED SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 J6 6 7 RED BLK RED BLK SENSOR 2 SENSOR 1 RED RED BLK SENSOR 3 SENSOR 4 BLK BLK RED RED RED BLK BLK SENSOR 8 SENSOR.
13 LE GEND Fig. 7 — Pre mierLink ™ Controller and Sensor Wiring — 33ZCT55S PT, 33ZCT56S PT, 33Z CT58SPT Space Temperature Se nsors; 33ZCSENSAT Supply Air Tempera ture Sensor; 33ZCSENCO2 (Outdoor.
14 Fig. 8 — PremierLink ™ Co ntrolle r Wiring — Combination Temperature and CO 2 Sensor — 33ZCT55C O2, 33 ZCT56CO2 NO TE: No wire is connected to c onnector J-5 pin 4. Y ou must relocat e a wire from an unused ter minal. T ypically one of the red wires from c onnector J-4 may be used for this purpos e.
15 NO TE: Remov e all un used red wires from J4 connector to pre v ent 24 v ac shor ting other components or ground. Inputs on J4 are 24 v ac. Red leads are voltage source.
16 NO TE: Remov e red wire f rom J4-9 to pre v ent 24 v ac shor ting out other components or ground. Inputs on J4 are 24 v ac. Red leads a re voltage source.
17 Fig. 11 — Typical Mounting Location for Supply Air Tempera ture (SAT) Sensor On Split Sys tem Units 8 7 6 5 4 32 1 2 1 HG 24 V AC OR 24 VDC NC ALARM RELA Y CONT ACTS COM NO } 0-10VDC SIG COM (J5-3) 4-20mA (J5-2) + + - + - Fig. 12 — Outdoor Air Quality (CO 2 ) Sensor (33ZCSENCO2) — Typical Wiring Dia gram Fig.
18 Connect to CCN Com m unication Bus — The PremierLink™ controller connects to the bus in a d aisy chain arrangemen t. Negative pins on each component m ust be connected to respective negative p ins and likewise positive p ins on each component must be connected to respective positive pins.
19 Mounting — Mount the enthalpy switch/receiver in a location where the outdoor air can be sampled (such as the outdoor air intake). The entha lpy switch/receiver is not a NEMA 4 encl o- sure and should be mounted in a location that is not exposed to outdoor elements such a s rain or snow .
20 Connect the 4-20 mA In terminal on the enthalpy switch/ receive r to the 4 -20 m A Ou t ter minal o n the ret urn air enth alpy sensor . Connect t he 24-36 VDC Out terminal on the enthalpy switch/rece ive r to the 24-36 VD C In t erminal on the return ai r enthalpy sensor .
21 W iri ng Enthalp y Sensors — T o wire the enthalpy sensor, per- form the following (see Fig. 24 a nd 25): NOTE: T o mount outdoor air sensor remotely , remove it from back of enthalpy control and follow steps 3 and 6.
22 Q7 6 9 B — Be cause the Honeyw ell adapter is de signed for a negative 4 to 20 mA input instead of a positive signal, the Q769B adapter requires a separate transformer a nd a current loop isolator to perform properly .
23 NOTE: If Pr em ier Lin k ™ Cont roller is grounded and actuator is grounded on common side , then common wire from PremierLink controller J9-2 is not needed.
24 Economizer wit h Johnson 4 to 20 mA Actua - tor — The PremierLink Controller can be connected to an economizer that us es a Johnso n 4 to 20 mA actuato r . DR I V E DI R E C T I ON — The actua tor drive direction is dependent upon the position of Switch 3 a nd the spring return direction.
25 Output 20 VDC at 25 mA Feedback 0 (2)-10 or 6-9 VDC Input 0 (2)-10 or 6-9 VDC, 0 (4)-20 mA 24 V AC/VDC COM (3) (5) (4) (2) (1) J9-1 TO 24V TRANSFORMER Gray White/Red Red Y ellow White WIRE HARNESS .
26 ST ART -U P Use the Carri er network communica tion software to start up and configure the Prem ierLink™ controller . Changes can be made using the ComfortWORKS ® soft- ware, ComfortVIEW™ software, or N etwork Service T ool.
27 keys which are the up arrow ( ), down arrow ( ), and keys. IN S T A L L A T I O N — The Navigator display module is intend- ed to be a mobile device, so the re are no holes in the device for permanent mounting. T he module has a magnetic mount that is strong enough to hold the device in place on any clea n, dry metal surf ace.
28 T o access the sub-mode to change the Unocc upied OA T Lockout Setpoint, press the down arrow to scroll down until the Navigator™ module display reads: SETP OA TL >NTLO UHDB T o view an expansion of the sub-mode, press the and keys simultaneously and the Navigator will display: >NTLO UNOCC.
29 Tab le 7 — Points Displ ay NO TE: Bold values i ndicate points that can be f orced through communications. SU P P L Y F AN ST A TU S — T his point displa ys the S upply Fan status if controller is configured to receive input from the Supply Fan.
30 HE A T S T A G E 2 — T he Heat Stage 2 point provide s the state of the Heating 2 output. Heating Stage 2: Display Units: Discrete ASCII Default V a lue: Off Display Range: Off/ On Network Ac cess: Read Only HEA T ST AGE 3, EXHAUST F AN , OR REVERSING V A L V E — This point di splays the commanded state of auxi l- iary output.
31 Table 8 — Thermostat Control Input Display AL A R M RE - A L A R M T I M E — This decision i s used to con- figure the number of minutes that will elapse bet ween re-alarms. A re-al arm occurs when the conditi on that caused the initial alarm continues to persist for the number of mi nutes specified.
32 DU R A T I O N — The Duration field indica tes how long the holiday will last (in days). Duration: Range: 0 to 365 Default V a lue: 0 As an example, i f a Holiday is configured for M onth 2, Day 5, Duration 2, then the Holiday will start February 5 and end February 7.
33 UNOCCUPIED HIGH — The Un oc cu pie d H igh se t po in t d e- scribes the high temperat ure limit of the space during Unoccu- pied mode. Unoccupied High: Units: Degrees F (D egrees C) Range: 45.
34 Table 14 — Service Configuration Selection ST AG ED C OOLING — The s t a g in g fun c t i on i s us e d f o r D X cooling (1 or 2 stages). The sta ging function uses the cooling submaster reference from the PID and c ompares the value to the supply air temperature to calculate the required number of output stages to energize.
35 The integral gain affects the PID calcula tion; an increa se will ma ke the IAQ submaste r referenc e change greater as t he error in indoor air quality increases. The integral gain should be selected to eliminate proportional droop without over shoot.
36 The DXCTLO should be turned OFF (to ignore the DXLOCK setpoint) in applications where there is either no OA T sensor (local or broadcast) or t he OA T sensor has failed. For V ersion 1 .3 — If there is a valid OA T sensor reading and DXCTLO is set t o “OFF”, compressor cool ing wi ll NOT be allowed.
37 PremierLink ™ Configurati on Screen — The PremierLink Configuration screen al low s the user to configure all functions. See T a ble 15. OP E R A T I N G M O D E — The Ope rat ing Mode function determines the operating mode of the PremierLink controller .
38 GLOBAL SC HEDULE BROADC AST — The Gl obal Sc hed- ule Broadcast setting confi g ures the controller t o broadcast or receive a global schedule. If se t to Y es, the controller will a ct as a global schedule master and its schedule will be broadcast to the CCN.
39 Low Refere nce spe cif ies Low Poin t of the Out door IAQ Sensor Range in ppm. Low Reference: Uni ts: PPM (parts per million) Range: 0 to 5000 Default V a lue: 0 High Reference specifies High Point of the Outdoor IAQ Sensor Range in ppm.
40 NEXT UNOCCUPIED DA Y — Th e N e xt Un o ccu pi e d Da y point displays the day of w eek when the next unoccupied peri- od will begin. This point is used with the Next Unoccupied T ime so the user will know when the next unoccupied period will occur .
41 IAQ PRE-OCCUP ANCY PURGE — Ind i ca tes tha t the pr e- occupancy purge mode is currently act ive. IAQ Pre-occupancy Purge: Display Range: No/Y es Default V a lue: No Netwo rk Ac cess: Read Only UNOCCUPIED FREE COOLING — In d i ca t e s th a t unoccu- pied free cooling is i n effect.
42 The A verage O ccupied Hea t Set Point displays t he Occupied Heat set point from the Linkage The rmostat. A verage Occupi ed Heat Set Point : Di splay Un its: Degrees F (Degrees C) Display Range: 0.
.
Manufactu rer reser ves the rig ht to dis continue , or chan ge at a ny time, spec ificati ons or des igns without notice an d wit hout inc urring obligations.
An important point after buying a device Carrier PREMIERLINK 33CSPREMLK (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Carrier PREMIERLINK 33CSPREMLK yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Carrier PREMIERLINK 33CSPREMLK - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Carrier PREMIERLINK 33CSPREMLK you will learn all the available features of the product, as well as information on its operation. The information that you get Carrier PREMIERLINK 33CSPREMLK will certainly help you make a decision on the purchase.
If you already are a holder of Carrier PREMIERLINK 33CSPREMLK, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Carrier PREMIERLINK 33CSPREMLK.
However, one of the most important roles played by the user manual is to help in solving problems with Carrier PREMIERLINK 33CSPREMLK. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Carrier PREMIERLINK 33CSPREMLK along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center